5 ACTUAL VALUES
5.2A1 STATUS
Õ
PATH: ACTUAL VALUES
n MOTOR STATUS
n [ENTER] for more
These messages describe the motor status at any given point in time. If the motor has been tripped and the 469 has not yet
been reset, the

MOTOR STATUS

both the Stator and Rotor Thermal Capacity Used. The values for
469 picks up on the overload curve.
Õ
PATH: ACTUAL VALUES
n LAST TRIP DATA
n [ENTER] for more
GE Multilin
Courtesy of NationalSwitchgear.com
Õ
A1 STATUS
MOTOR STATUS
ð
MOTOR STATUS:
ENTER
ESCAPE
Stopped
MOTOR THERMAL
ESCAPE
CAPACITY USED: 0%
MESSAGE
ESTIMATED TRIP TIME
ESCAPE
ON OVERLOAD: Never
MESSAGE
MOTOR SPEED:
ESCAPE
Low Speed
MESSAGE
value will be "Tripped". The
Õ×
A1 STATUS
LAST TRIP DATA
ð
CAUSE OF LAST TRIP:
ENTER
No Trip to Date
ESCAPE
TIME OF LAST TRIP:
ESCAPE
09:00:00.00
MESSAGE
DATE OF LAST TRIP:
ESCAPE
Jan 01 1995
MESSAGE
MOTOR SPEED DURING
ESCAPE
TRIP: Low Speed
MESSAGE
TACHOMETER
ESCAPE
PRETRIP: 3600 RPM
MESSAGE
A:
0
ESCAPE
C:
0
MESSAGE
MOTOR LOAD:
ESCAPE
0.00 x FLA PreTrip
MESSAGE
CURRENT UNBALANCE
ESCAPE
MESSAGE
PRETRIP: 0%
GROUND CURRENT
ESCAPE
PRETRIP: 0.00 Amps
MESSAGE
A:
0
ESCAPE
C:
0
A Diff.PreTrip
MESSAGE
469 Motor Management Relay
Range: Tripped, Stopped, Starting, Running, Overload
Range: 0 to 100%
Range: 0 to 10000 sec., Never
Range: HIgh Speed, Low Speed
Seen only if Two Speed Motor feature is enabled
MOTOR THERMAL CAPACITY USED
ESTIMATED TRIP TIME ON OVERLOAD
Range: No Trip to Date, Incomplete Sequence,
Remote Trip, Speed Switch, Load Shed,
Pressure Switch, Vibration Switch, General
Sw, Overload, Short Circuit, Mechanical Jam,
Undercurrent, Current Unbalance, Ground
Fault,
Tachometer, RTD #1 to #12, Undercurrent,
Overvoltage, Phase Reversal, Frequency,
Reactive Power, Power Factor, Underpower,
Analog Inputs 1 to 4
Range: hour:min:sec
Range: Month Day Year
Range: High Speed, Low Speed
Seen only if Two-Speed Motor is enabled
Range: 0 to 3600 RPM. Seen only if an Assignable
Digital Input is programmed as Tachometer.
Range: 0 to 100000 A
B:
0
A PreTrip
Range: 0.00 to 20.00 x FLA
Range: 0 to 100%
Range: 0.0 to 5000.0 A
Range: 0 to 5000 A. Not seen if Differential CT is
B:
0
programmed as None
5.2 A1 STATUS
5.2.1 MOTOR STATUS
reflects an integrated value of
appear whenever the
5.2.2 LAST TRIP DATA
Phase
Differential,
Acceleration,
5-3
5