Test Output Relays; Test Analog Output - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

4.14 S13 469 TESTING
Õ×
PATH: SETPOINTS
S13 469 TESTING
n TEST OUTPUT RELAYS
n [ENTER] for more
In addition to the simulation modes, the
that the output relays are functioning correctly.
The output relays can only be forced to operate only if the motor is stopped and there are no trips, alarms, or start blocks
active. If any relay is forced to operate, the relay will toggle from its normal state when there are no trips, alarms, or blocks
to its active state. The appropriate relay indicator will illuminate at that time. Selecting "Disabled" places the output relays
back in service. If the 469 measures phase current or control power is cycled, the
will automatically become disabled and the output relays will revert back to their normal states.
If any relay is forced, the 469 In Service LED will flash, indicating that the 469 is not in protection mode.
4
Õ×
PATH: SETPOINTS
S13 469 TESTING
n TEST ANALOG OUTPUT
n [ENTER] for more
In addition to the simulation modes, the
that the analog outputs are functioning correctly.
The analog outputs can only be forced if the motor is stopped and there are no trips, alarms, or start blocks active. When
the
FORCE ANALOG OUTPUTS FUNCTION
or 0 to 1 mA range. Selecting "Disabled" places all four analog output channels back in service, reflecting the parameters
programmed to each. If the 469 measures phase current or control power is cycled, the
is automatically disabled and all analog outputs revert back to their normal state.
Any time the analog outputs are forced, the 469 In Service LED will flash, indicating that the 469 is not in protection mode.
4-80
Courtesy of NationalSwitchgear.com
Õ×

TEST OUTPUT RELAYS

ð
FORCE OPERATION OF
ENTER
ESCAPE
RELAYS: Disabled
setpoint group may be used during startup or testing to verify
TEST OUTPUT RELAYS
Õ×

TEST ANALOG OUTPUT

ð
FORCE ANALOG OUTPUTS
ENTER
ESCAPE
FUNCTION: Disabled
ANALOG OUTPUT 1
ESCAPE
FORCED VALUE: 0%
MESSAGE
ANALOG OUTPUT 2
ESCAPE
FORCED VALUE: 0%
MESSAGE
ANALOG OUTPUT 3
ESCAPE
FORCED VALUE: 0%
MESSAGE
ANALOG OUTPUT 4
ESCAPE
FORCED VALUE: 0%
MESSAGE
setpoint group may be used during startup or testing to verify
TEST ANALOG OUTPUT
is "Enabled", the output reflects the forced value as a percentage of the 4 to 20 mA
469 Motor Management Relay
4.14.4 TEST OUTPUT RELAYS
Range: Disabled, R1 Trip, R2 Auxiliary, R3 Auxiliary, R4
Alarm, R5 Block, R6 Service, All Relays, No
Relays
FORCE OPERATION OF RELAYS
4.14.5 TEST ANALOG OUTPUT
Range: Enabled, Disabled
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
FORCE ANALOG OUTPUTS FUNCTION
4 SETPOINTS
setpoint
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents