A.3 CURRENT TRANSFORMERS
APPENDIX A
A.3 CURRENT TRANSFORMERS
A.3.1 GROUND FAULT CTS FOR 50:0.025 A CT
A
CTs that are specially designed to match the ground fault input of GE Multilin motor protection relays should be used to
ensure correct performance. These CTs have a 50:0.025A (2000:1 ratio) and can sense low leakage currents over the relay
setting range with minimum error. Three sizes are available with 3½", 5½", or 8" diameter windows.
HGF3 / HGF5
HGF8
DIMENSIONS
DIMENSIONS
808710A1.CDR
A-4
469 Motor Management Relay
GE Multilin
Courtesy of NationalSwitchgear.com