5.2 A1 STATUS
5
Immediately prior to issuing a trip, the 469 takes a snapshot of motor parameters and stores them as pre-trip values that
allow for troubleshooting after the trip occurs. The
screen defaults to that message. All trip features are automatically logged as date and time stamped events as they occur.
This information may include motor speed (2-Speed feature or Assignable Digital Input), phase and ground currents, RTD
temperatures, voltages, frequency, power quantities, and analog inputs. This information can be cleared using the
Õ×
SETUP
CLEAR DATA
Phase, differential, and ground currents are recorded 1 cycle prior to the trip. All other pre-trip data is recorded
50 ms prior to the trip. Thus some values will not be recorded upon instantaneous trips during a start if the trip is
NOTE
less than 50 ms.
5-4
Courtesy of NationalSwitchgear.com
HOTTEST STATOR RTD
ESCAPE
MESSAGE
RTD #1: 0°C PreTrip
HOTTEST STATOR RTD
ESCAPE
RTD #7: 0°C PreTrip
MESSAGE
HOTTEST STATOR RTD
ESCAPE
RTD #11: 0°C PreTrip
MESSAGE
AMBIENT RTD
ESCAPE
RTD#12: 0°C PreTrip
MESSAGE
Vab:
ESCAPE
Vca:
MESSAGE
Van:
ESCAPE
Vcn:
MESSAGE
PRETRIP SYSTEM
ESCAPE
FREQUENCY: 0.00 Hz
MESSAGE
0 kW
ESCAPE
MESSAGE
0 kvar
POWER FACTOR
ESCAPE
PreTrip: 0.00
MESSAGE
ANALOG INPUT 1
ESCAPE
PreTrip: 0 Units
MESSAGE
ANALOG INPUT 2
ESCAPE
PreTrip: 0 Units
MESSAGE
ANALOG INPUT 3
ESCAPE
PreTrip: 0 Units
MESSAGE
ANALOG INPUT 4
ESCAPE
PreTrip: 0 Units
MESSAGE
CAUSE OF LAST TRIP
Õ×
setpoint.
CLEAR TRIP COUNTERS
469 Motor Management Relay
Range: –50 to 250°C. Seen only if at least 1 RTD
programmed as Stator
Range: –50 to 250°C. Seen only if at least 1 RTD
programmed as Bearing
Range: –50 to 250°C. Seen only if at least 1 RTD
programmed as Other
Range: –50 to 250°C. Seen only if at least 1 RTD
programmed as Ambient
Range: 0 to 20000 V. Not seen if VT Connection is
0
Vbc:
0
programmed as None
0
V PreTrip
Range: 0 to 20000 V. Not seen if VT Connection is
0
Vbn:
0
programmed as Wye
0
V PreTrip
Range: 0.00, 20.00 to 120.00 Hz. Not seen if VT
Connection is programmed as None
Range: –50000 to 50000 kVA. Not seen if VT
0 kVA
Connection is programmed as None
PreTrip
Range: 0.01 to 0.99 Lead or Lag, 0.00, 1.00. Not seen
if VT Connection is programmed as None
Range: –50000 to 50000. Not seen if VT Connection
is programmed as None
Range: –50000 to 50000. Not seen if VT Connection
is programmed as None
Range: –50000 to 50000. Not seen if VT Connection
is programmed as None
Range: –50000 to 50000. Not seen if VT Connection
is programmed as None
message is updated with the current trip and the
5 ACTUAL VALUES
S1 469
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents