6 COMMUNICATIONS
Table 6–2: MEMORY MAP DATA FORMATS (Sheet 11 of 12)
FORMAT
TYPE
DEFINITION
CODE
bit 9
Motor Starting
bit 10
Motor Running
bit 11
Overload Pickup
bit 12
Unbalance Pickup
bit 13
Ground Pickup
bit 14
Hot RTD
bit 15
Loss of Load
FC141
Unsigned
OUTPUT RELAY STATUS
16 bit integer
bit 0
R1 Trip
bit 1
R2 Auxiliary
bit 2
R3 Auxiliary
bit 3
R4 Alarm
bit 4
R5 Block Start
bit 5
R6 Service
bit 6 – bit 15
Not Used
FC142
Unsigned
TRIP COIL SUPERVISION SELECTION
16 bit integer
0
Disabled
1
S2 Close
2
S2 Open/Close
FC143
Unsigned
SINGLE VT SELECTION
16 bit integer
0
Off
1
AN (Wye) AB (Delta)
2
BN (Wye) BC (Delta)
3
CN (Wye) N/A (Delta)
GE Multilin
Courtesy of NationalSwitchgear.com
Table 6–2: MEMORY MAP DATA FORMATS (Sheet 12 of 12)
FORMAT
TYPE
CODE
FC144
Unsigned
16 bit integer
0
1
2
3
FC145
Unsigned
16 bit integer
0
1
FC146
Unsigned
16 bit integer
0
1
2
FC147
Unsigned
16 bit integer
0
1
FC148
Unsigned
16 bit integer
0
1
469 Motor Management Relay
6.3 MEMORY MAP
DEFINITION
PULSED OUTPUT RELAY SELECTION
Off
Auxiliary2
Auxiliary3
Alarm
ANALOG IN DIFFERENTIAL COMPARISON
% Difference
Absolute Difference
ANALOG IN DIFFERENTIAL LOGIC
1>2 (or 3>4)
2>1 (or 4>3)
1<>2 (or 3<>4)
ANALOG IN DIFFERENTIAL ACTIVE WHEN
Always
Start/Run
TORQUE DISPLAY UNITS
Newton-meter
Foot-pound
6
6-51