HMI Interface

The controller module is equipped with an HMI Interface for
the connection of HMIs, e.g., XI582 Operator Interface or a
laptop (with XL-Online/CARE).
Fig. 52
HMI interface, Tx LED (1) and Rx LED (2)
HMI interface LEDs on RJ45 socket
Tx (1)
The controller is transmitting data to the HMI
flickering
Rx (2)
The controller is receiving data from the HMI
flickering
Table 30 HMI interface LEDs
HMI interface Signals on RJ45 socket
Pin
Signal type
1
-
2
Receive
3
Transmit
4
-
5
Signal ground
6
-
7
5 V
8
-
Table 31 Signals of the HMI interface
NOTICE
Equipment damage!
Make sure that the controller is not connected to earth
ground.
If nonetheless earth grounding is required, make sure
that only terminal 2 is connected to earth ground.
Terminal 1 must not be connected to earth ground. See
also Appendix 1.
EN1B-0375GE51 R0308

Alarm and Power LEDs

The CLLIONLC01 Controller Module is equipped with an
alarm LED and a power LED.
Fig. 53
Alarm LED (1) and power LED (2)
Alarm LED (1, red)
Off
Normal operation
On
Watchdog alarm output is powered
• The controller has encountered a
hardware problem
• The application has a fault
• The controller has been powered up
without an application or the operator has
manually stopped the application,
e.g., using XL-Online.
In this case, the LED will light up
13 minutes after power-up without
application
Flashing
The watchdog alarm output has not yet been
powered, although the controller has
encountered a problem.
The controller performs a warm start.
If problem persists, the LED will become lit
constantly, see above.
See section "Troubleshooting" on page 68.
Table 32 Controller alarm LED
36