2: Requirements For Central Station Fire Alarm Systems; 3: Requirements For Local Protected Fire Alarm Systems; 4: Requirements For Remote Station Protected Fire Alarm Systems; 5: Requirements For The Installation Of Carbon Monoxide (Co) Detection And Warning Equipment, Nfpa 720 - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 3 hours. For UL certified installations this
number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications
whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
The system allows the Alarm Verification time to be set from 60 to 250 seconds. For UL certified installations the setting must be a
minimum of 60 seconds.
The system allows the Auto-resound time to be set to 24 or 4 hours. For UL certified installations that are utilizing SWIFT devices,
the value must be set to 4 hours.
Call forwarding shall not be used.
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be
used.
P.A.S(positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm Systems
1.
Use both phone lines. Enable phone line monitors for both lines.
2.
You must program a phone number and a test time so that the IFP-300/ECS shall automatically initiate and complete a test signal
transmission sequence to its associated receiver at least once every 6 hrs. The AC Loss Hours option must be set from 1-3 hours.
3.
If using wired Ethernet or cellular, you must program the corresponding account/subscriber ID and a test time so that the FACP
shall automatically initiate a test signal transmission sequence to its associated receiver at least once every 6 hrs.
2.2.3 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems
Minimum system requirements are one Honeywell addressable initiating device and either a 5220, Keltron 3158 or the built-in Digital
Alarm Communicator Transmitter (DACT).
1.
Do not exceed the current load restrictions shown in Section 3.7.5.
2.
The AC Loss Hours option must be set from 1-3 hours.
2.2.5 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station.
2.2.6 NFPA Requirements
The following is the minimum configuration to meet the NFPA requirements.
Model/Module
IFP-300CB(red)
IFP-300BCB(black)
068080
6861BIA/6861GIA
5815XL
6815
SK-NIC
SK-FML/ -FSL
7644
5220
Keltron 3158
Cell-Mod/Cell-Cab-
1
SK
Y = YES, N = NO, O = OPTIONAL
1.
1.When configured for Emergency Relocation and Evacuation Equipment the system must meet Local configuration
Model IFP 300) with a minimum of one amplifier (Model VIP-50/125 or ECS-50W/ECS-125W or EVS-50W/EVS-125W or
ECS-INT50W) and one Voice Control Module (Model VIP VCM / ECS-VCM/ EVS-VCM).
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Description
Local
Enclosure
Y
Motherboard
Y
4 x 40 display
Y
SLC Expander
O
SLC Expander
O
Network card
O
Fiber module
O
Pol Rev device
N
City tie, Pol. Rev
N
Device
Rev Pol Module
N
Cellular
N
transmitter
Table 2.1
NFPA Requirements for IFP-300
Remote
Releasing
Auxiliary
Station
Y
Y
Y
Y
Y
Y
O
O
O
O
O
O
O
O
N
Y
N
Y
N
Y
N
Y
Central
Emergency
Station
Signaling
Y
Y
Y
Y
Y
Y
Y
Y
Y
O
O
O
O
O
O
O
O
O
O
O
O
N
N
N
Y
N
N
Y
N
N
N
Y
N
6