Terminal Data For The Power Cables - ABB ACS180-04S-03A7-1 Hardware Manual

Table of Contents

Advertisement

Terminal data for the power cables

The first table shows the terminal data in SI units. The second table shows the
terminal data in imperial units.
ACS180-
L1, L2, L3, T1/U, T2/V, T3/W, R-, R+/
04...
Minimum
(sol-
id/stran-
ded)
mm 2
1-phase U n = 208 ... 240 V
-02A4-1
0.2/0.2
-03A7-1
0.2/0.2
-04A8-1
0.2/0.2
-06A9-1
0.2/0.2
-07A8-1
0.2/0.2
-09A8-1
0.2/0.2
-12A2-1
0.2/0.2
3-phase U n = 208 ... 240 V
-02A4-2
0.2/0.2
-03A7-2
0.2/0.2
-04A8-2
0.2/0.2
-06A9-2
0.2/0.2
-07A8-2
0.2/0.2
-09A8-2
0.2/0.2
-15A6-2
0.2/0.2
-17A5-2
0.2/0.2
-25A0-2
0.5/0.5
-033A-2
0.5/0.5
-048A-2
0.5/0.5
-055A-2
0.5/0.5
3-phase U n = 380 ... 415 V
-01A8-4
0.2/0.2
UDC+
Maximum
Tightening
torque
(sol-
id/stran-
ded)
mm 2
N·m
6/4
0.5...0.6
6/4
0.5...0.6
6/4
0.5...0.6
6/6
0.5...0.6
6/6
0.5...0.6
6/6
0.5...0.6
6/6
0.5...0.6
6/4
0.5...0.6
6/4
0.5...0.6
6/4
0.5...0.6
6/6
0.5...0.6
6/6
0.5...0.6
6/6
0.5...0.6
6/6
0.5...0.6
6/6
0.5...0.6
10/6
1.2...1.5
10/6
1.2...1.5
25/16
2.5...3.7
25/16
2.5...3.7
6/4
0.5...0.6
Technical data 125
PE
Minimum
Maximum
(sol-
(sol-
id/stran-
id/stran-
ded)
ded)
mm 2
mm 2
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
0.5
16/16
0.5
16/16
0.5
16/16
0.5
16/16
4/2.5
6/4
Tightening
torque
N·m
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2

Advertisement

Table of Contents
loading

Table of Contents