154 Technical data
Terminal and lead-through data for the power cables
The locations and sizes of lead-throughs are shown by the dimension drawings delivered
with the drive, and the dimension drawing examples in this manual.
Terminal data for the supply and inverter control units
See chapter
Control units of the drive (page
Contact data for main contactor/breaker control
■
General
The main contactor or breaker is controlled by the drive through relay K3. The relay has
one normally-open (NO) and one normally-closed (NC) contact.
Emergency stop options add a relay (K640) to the drive. To trip the main breaker upon an
emergency stop, one of the output switchover contacts of K640 must be wired to the
undervoltage coil.
The contacts of both relays are wired to a terminal block in the drive cubicle; see the
drive-specific circuit diagrams for details. The external voltage switched by the contacts is
to be connected to the same terminal block.
■
K3 contact data
•
Rated operational AC current (I
•
24...127 V, 50/60 Hz: 6 A
•
220...240 V, 50/60 Hz: 4 A
•
400...440 V, 50/60 Hz: 3 A
•
500 V, 50/60 Hz: 2 A
•
690 V, 50/60 Hz: 2 A
•
Rated making/breaking capacity (IEC/EN 60947-5-1 AC 15): 10 × I
•
Rated operational DC current (I
•
24 V DC: 6 A / 144 W
•
48 V DC: 2.8 A / 134 W
•
72 V DC: 1 A / 72 W
•
110 V DC: 0.55 A / 60 W
•
125 V DC: 0.55 A / 69 W
•
220 V DC: 0.27 A / 60 W
•
250 V DC: 0.27 A / 68 W
•
400 V DC: 0.15 A / 60 W
•
500 V DC: 0.13 A / 65 W
•
600 V DC: 0.1 A / 60 W
•
Rated short-time withstand current (): 100 A for 1.0 s, 140 A for 0.1 s
•
Minimum switching capacity: 12 V / 3 mA
■
K640 contact data
•
Switching power: 3 VA or 3 W minimum, 2000 VA or 200 W maximum
•
Switching capacity, AC (IEC/EN 60947-5-1 AC 15):
99).
) (IEC/EN 60947-5-1 AC 15):
e
) (IEC/EN 60947-5-1 DC 13):
e
AC
e