Special Plc Functions; Section Changeover - JUMO mTRON T Operating Manual

Measuring, control, and automation system process engineering application
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

3.8

Special PLC functions:

3.8.1

Section changeover

With section changeover, moving to the next program section occurs once the actual value
(core temperature) has reached the setpoint value. Here, the section time can serve as an ad-
ditional criterion for the changeover.
The setpoint value for the section changeover (core setpoint value) must be selected in the pro-
gram generator configuration and be specified in the program. The different combinations for
the
section
"Time != 0 or Setp. != NoInput").
The following setting is required for PLC configuration:
Actual value (parameter 5): select analog signal to supply the actual value.
CPU > Configuration level > PLC configuration
In this example, input 3 (AI03) of the 4-channel analog input module (Analog In 4x) is used as
the actual value for the section changeover (P1 X changeover) (the same input as for display-
ing the actual value, see Chapter 3.2 "Actual values", page 43).
changeover
(time/setpoint
3 Configuration
value)
are
supported
(except