Woodward 723PLUS Technical Manual page 59

Two-engine redundant lon torque sharing marine propulsion application
Table of Contents

Advertisement

Manual 26482
08 CLON CH2 ERROR (*T/F)—Set this value "FALSE" if no minor alarm output
is desired when a Control LON Channel 2 error is detected. Set this value
"TRUE" if a minor alarm output is desired when a Control LON Channel 2 error is
detected.
09 CLON CH1&2 ERROR (*T/F)—Set this value "FALSE" if no minor alarm
output is desired when both Control LON Channel 1 and 2 errors are detected.
Set this value "TRUE" if a minor alarm output is desired when both Control LON
Channel 1 and 2 errors are detected.
10 PID @ LOW LEVEL (*T/F)—Set this value "FALSE" if no minor alarm output
is desired when PID At Zero Fault occurs. Set this value "TRUE" if a minor alarm
output is desired when PID At Zero Fault occurs.
11 OVERSPEED (*T/F)—Set this value "FALSE" if no minor alarm output is
desired when engine overspeed occurs. Set this value "TRUE" if a minor alarm
output is desired when engine overspeed occurs.
12 CLUTCH FAIL (*T/F)—Set this value "FALSE" if no minor alarm output is
desired when a clutch engaged contact is not received within the CLUTCH SYNC
TIME. Set this value "TRUE" if a minor alarm is desired when the clutch engaged
contact is not received within the CLUTCH SYNC TIME.
13 ACTUATOR MODE (MECH GOV) (*T/F)—Set this value "FALSE" if no minor
alarm output is desired when the ACTUATOR MODE discrete input contact is
open. Set this value "TRUE" if a minor alarm is desired when the ACTUATOR
MODE discrete input contact is closed.
14 TORQ DEV ERROR (*T/F)—Set this value "FALSE" if no minor alarm output
is desired when a TORQUE DEVIATION is sensed. Set the value "TRUE" if a
minor alarm is desired.
15 ACT CUR DEV ERROR (*T/F)—Set this value "FALSE" if no minor alarm
output is desired when an ACTUATOR CURRENT DEVIATION is sensed. Set
the value "TRUE" if a minor alarm is desired.
E**ALARM/SD CONFIGURE**
01 ALARM DELAY TIME (*0.01–60.0)—Set this value for the duration that an
analog input must be outside the normal operating range (below 2.0 mA for the
low side or above 22 mA for the high side) before it is considered failed. The
units for this value are seconds.
02 OPEN CNT ON MIN ALM (*T/F)—If this value is set "FALSE", the minor alarm
relay (relay #1) will energize, closing the contacts at terminals #3 and #4 when a
minor alarm occurs. If this value is set "TRUE", the minor alarm relay (relay #1)
will de-energize, opening the contacts at terminals #3 and #4 when a minor alarm
occurs. Remember that for any of the minor alarms to be annunciated by the
minor alarm output, it must first be enabled while under configure header
D**CONFIG MINOR ALARMS**.
03 OPEN CNT ON MAJ ALM (*T/F)—If this value is set "FALSE", the major
alarm relay (relay #2) will energize, closing the contacts at terminals #5 and #6
when a major alarm occurs. If this value is set "TRUE", the major alarm relay
(relay #2) will de-energize, opening the contacts at terminals #5 and #6 when a
major alarm occurs. Remember that for any of the major alarms to be
annunciated by the major alarm output, it must first be enabled while under
configure header C**CONFIG MAJOR ALARMS**.
Woodward
723PLUS Digital Marine Control
49