Woodward 723PLUS Original Instructions Manual

Woodward 723PLUS Original Instructions Manual

Digital speed control for reciprocating engines - performance control 598
Hide thumbs Also See for 723PLUS:
Table of Contents

Advertisement

Product Manual 26043
(Revision B, 7/2008)
Original Instructions
723PLUS Digital Speed Control for
Reciprocating Engines—
Performance Control '598'
8280-598
Installation and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Woodward 723PLUS

  • Page 1 Product Manual 26043 (Revision B, 7/2008) Original Instructions 723PLUS Digital Speed Control for Reciprocating Engines— Performance Control ‘598’ 8280-598 Installation and Operation Manual...
  • Page 2 Revisions—Changes in this publication since the last revision are indicated by a black line alongside the text. Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly undertaken.
  • Page 3: Table Of Contents

    OINTS   Introduction ......................24   Watch Window Generic PC Interface ..............24   723PLUS Performance Control ‘598’ Control View ..........25   Hand Held Programmer and Menus ..............39   Configuration Menu Descriptions ................. 42   Service Menu Descriptions ................... 52 4.
  • Page 4 723PLUS Performance Control ‘598’ Manual 26043 Contents 6. T ............. 103  HAPTER ROUBLESHOOTING   General .......................103   Troubleshooting Procedure ................103   Control Test and Calibration ................103   Conclusion of Test and Calibration Procedures ..........107 7. P ......108  HAPTER RODUCT...
  • Page 5 Figure A-2. 723PLUS RS-422 Connections with Optional Termination at   Receiver ..................112   Figure A-3. 723PLUS RS-485 Connections with Optional Termination ..... 113   Figure A-4. RS-422 Terminator Locations ............113 Figure A-5. Preferred Multipoint Wiring Using Shielded Twisted-pair Cable with a  ...
  • Page 6: Warnings And Notices

    Start-up On- and off-highway Mobile Applications: Unless Woodward's control functions as the supervisory control, customer should install a system totally independent of the prime mover control system that...
  • Page 7: Electrostatic Discharge Awareness

    Do not touch the components or conductors on a printed circuit board with your hands or with conductive devices. To prevent damage to electronic components caused by improper handling, read and observe the precautions in Woodward manual 82715 , Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards, and Modules.
  • Page 8 723PLUS Performance Control ‘598’ Manual 26043 Woodward...
  • Page 9: Chapter 1. General Information

    723PLUS Performance Control ‘598’ Chapter 1. General Information Introduction This manual describes the Woodward 723PLUS Digital Industrial Speed/ Performance Control ‘598’, model 8280-598 (low voltage). Declaration of Incorporation In accordance with the EMC Directive 89/336/EEC and its amendments, this controlling device, manufactured by the Woodward Governor Company, is applied solely as a component to be incorporated into an engine prime mover system.
  • Page 10: Control Options

    D connectors. Control Options Each 723PLUS control requires 40 W of power. A nominal current in-rush of 7 A is possible. Acceptable input voltage range is 18 to 40 Vdc. Discrete input voltages provide on/off command signals to the electronic control, such as Raise Speed, Lower Speed, etc.
  • Page 11 The two communication ports (J2 and J3) and the LON # 1 data channel allow for digital communications between external Modbus compatible devices and Woodward LinkNet I/O modules. Up to 9 LinkNet modules have been designated for use and can be connected to the LON # 1 channel. The inputs and outputs of these modules can be read and controlled with Modbus compatible devices connected to communication ports J2 and J3.
  • Page 12: Figure 1-1. 723Plus Digital Speed Control

    723PLUS Performance Control ‘598’ Manual 26043 Figure 1-1. 723PLUS Digital Speed Control Woodward...
  • Page 13: Figure 1-2. Watch Window Display

    Manual 26043 723PLUS Performance Control ‘598’ Figure 1-2. Watch Window Display Woodward...
  • Page 14: Figure 1-3. Hand Held Programmer

    723PLUS Performance Control ‘598’ Manual 26043 Figure 1-3. Hand Held Programmer Woodward...
  • Page 15: Figure 1-4. Typical 723Plus Connections

    Manual 26043 723PLUS Performance Control ‘598’ Figure 1-4. Typical 723PLUS Connections Woodward...
  • Page 16: Figure 1-5A. Control Wiring Diagram

    723PLUS Performance Control ‘598’ Manual 26043 Figure 1-5a. Control Wiring Diagram Woodward...
  • Page 17: Figure 1-5B. Control Wiring Diagram

    Manual 26043 723PLUS Performance Control ‘598’ Figure 1-5b. Control Wiring Diagram Woodward...
  • Page 18: Chapter 2. Installation

    Power Requirements The low voltage version of the 723PLUS Digital Speed/Performance Control ‘598’ requires a voltage source of 18 to 40 Vdc. To prevent damage to the control, do not exceed the input voltage range.
  • Page 19: Internal Jumpers

    723PLUS Performance Control ‘598’ Internal Jumpers The 723PLUS control has ten, two-position internal jumpers (JPR1 through JPR20) located on the top of the printed circuit board. If you need to change any jumper to match your control needs, be sure to read Electrostatic Discharge Awareness (p.iv), before proceeding.
  • Page 20: Figure 2-1. 723Plus Control Internal Jumpers

    723PLUS Performance Control ‘598’ Manual 26043 Figure 2-1. 723PLUS Control Internal Jumpers Where shielded cable is required, cut the cable to the desired length and prepare the cable as instructed below. Strip outer insulation from BOTH ENDS, exposing the braided or spiral wrapped shield.
  • Page 21 Power supply output must be low impedance (for example, directly from batteries). DO NOT power the control from high-voltage sources with resistors and zener diodes in series with the control power input. The 723PLUS control contains a switching power supply which requires a current surge (7 A) to start properly.
  • Page 22 To prevent possible damage to the control or poor control performance resulting from ground loop problems, we recommend using current-loop isolators if the 723PLUS control's analog inputs and outputs must both be used with non-isolated devices. A number of manufacturers offer 20 mA loop isolators.
  • Page 23 Manual 26043 723PLUS Performance Control ‘598’ Analog Output #1 (Terminals 15/16) Analog output #1 can be configured several different ways depending on the application needs. The output current is hardware configurable for either 0 to 1 mA or 4 to 20 mA. This current signal is supplied to terminals 15(+) and 16(–).
  • Page 24 LON #2 is not used. DO NOT CONNECT. Discrete Inputs (Terminals 29—36) Discrete inputs are the switch input commands to the 723PLUS control. They interact in such a way as to allow engine control under a variety of conditions. Voltage is supplied to the discrete input terminal when an input switch or relay contact closes.
  • Page 25 Manual 26043 723PLUS Performance Control ‘598’ In systems which provide an external low voltage source to power the 723PLUS control (or other systems where external low voltage dc power is available), the discrete inputs may be powered by this external low voltage. The voltage source used must be capable of supplying 100 mA at a voltage level of 18 to 40 Vdc.
  • Page 26 723PLUS Performance Control ‘598’ Manual 26043 Raise Air Manifold Pressure (Input C; Terminal 31) The input switch or relay contact used to activate the Raise Air Manifold Pressure function connects to terminal 31 (Discrete Input C). This discrete input changes the control operation by increasing the air manifold pressure reference ramp.
  • Page 27 Manual 26043 723PLUS Performance Control ‘598’ Lower Speed Contact (Input F; Terminal 34) The input switch or relay contact used to activate the Lower Speed command connects to terminal 34 (Discrete Input F). This discrete input changes the control operation by decreasing the speed reference ramp. The ramp can decrease only to a software adjusted LOWER SPEED limit.
  • Page 28 723PLUS Performance Control ‘598’ Manual 26043 Air Manifold Pressure Input (Signal Input #1; Terminals 42/43) Connect an air manifold pressure transmitter to Signal Input #1. The input signal must be an isolated high-quality signal. By configuration, this input is used in the air/fuel ratio, ignition timing, and turbocharger air assist controls, and for speed control fuel limiting.
  • Page 29 Communication Ports J2 and J3 Communication Ports J2 and J3 are used to connect two separate Modbus devices to the 723Plus control. These devices are used to read control parameters as well as read inputs from connected LinkNet nodes. The Modbus device connected to J3 can additionally drive LinkNet nodes and also drive certain 723Plus control parameters.
  • Page 30 Modbus Analog Write Address 0005 allows control of the speed reference. The signed 16-bit integer must be scaled as RPM for communication (that is, to produce a 330 RPM output from the 723Plus a value of 330 must be applied to address 4:0005).
  • Page 31: Installation Checkout Procedure

    Manual 26043 723PLUS Performance Control ‘598’ Installation Checkout Procedure With the installation complete as described in this chapter, do the following checkout procedure before beginning set point entry (Chapter 3) or initial start-up adjustments (Chapter 4). Visual inspection Check the linkage between the actuator and fuel metering device for looseness or binding.
  • Page 32: Chapter 3. Entering Control Set Points

    Watch Window Generic PC Interface Watch Window was developed by Woodward to be a ServLink client software product that provides a generic PC interface to any 723PLUS control. It is a very powerful setup, testing, and troubleshooting tool. Watch Window provides a...
  • Page 33: 723Plus Performance Control '598' Control View

    Monitoring parameter updates are very fast. Tunable values may be changed directly and saved in the controller’s EEPROM. Tunable values may also be saved to a file. Tunables from a file can be loaded into the 723PLUS. Control View communicates with the control through RS-232/RS-422 cable connection to port J1, which is configured as a point-to-point only ServLink server.
  • Page 34 723PLUS Performance Control ‘598’ Manual 26043  Configure Mode This mode is used to setup options that cannot be changed while the controller is in use (e.g., the number of teeth). Switching to configure mode will cause an I/O lockout. A confirmation dialog box appears so that the control is not accidentally placed in configuration mode.
  • Page 35 Manual 26043 723PLUS Performance Control ‘598’ Start-up Screen The following Start-up Screen appears when the 723PLUS Performance Control ‘598’ Control View is opened. This shows the Monitor Shutdown screen and displays the current status of all shutdowns. An Alarm Reset button is provided to reset any control alarms and shutdowns that have been cleared.
  • Page 36 723PLUS Performance Control ‘598’ Manual 26043 The following is an example of right clicking to select and move to the “Thermocouple” screen which is a sub-screen of “LinkNet” and “Monitor”. It displays the full lists of other LinkNet sub-screens and Monitor sub-screens as well as all Main screens (including those that are hidden).
  • Page 37 Manual 26043 723PLUS Performance Control ‘598’ The following is the same Fuel Limiter screen with the Fuel Limiter Settings sub- tab open. The main portion of this screen remains the same. The sub-tab exposes specific Fuel Limiter setting values with a set of raise/lower arrows.
  • Page 38 Service Mode) to save the control settings and to reset the control.  Save As Config File will dump all settings from the 723PLUS controller EEPROM into a Configuration File. To prevent possible damage to the engine resulting from improper control settings, make sure you save the set points before removing power from the control.
  • Page 39 Manual 26043 723PLUS Performance Control ‘598’ 2D and 3D Curves The 2D and 3D curve screens are unique. The Torque Limit Curve sub-screen with tabulated values and raise/lower arrows was shown earlier on the Fuel Limiter screen. The following shows a different way of viewing and changing this same curve as a graph instead of as tabulated settings.
  • Page 40 723PLUS Performance Control ‘598’ Manual 26043 Holding the cursor over a curve breakpoint displays the coordinates, in (x,y) format, for that specific point as shown below. Right clicking on a breakpoint and selecting “properties” will pop up a “Point Adjustment” window for that point as shown below.
  • Page 41 Manual 26043 723PLUS Performance Control ‘598’ The following is an example of a 3D curve. This is the fuel gas header pressure (FGH) versus air manifold pressure (AMP) versus engine speed (RPM) curve in x, y, z format. X (FGH) and Z (RPM) are curve inputs and Y (AMP) is the curve output.
  • Page 42 723PLUS Performance Control ‘598’ Manual 26043 In addition, the following setup dialog for a 3D graph allows setting the angle of rotation and turning grid lines and plane projections on or off. Trends Purpose: The purpose of a Trend Graph is to provide a visual relational representation of data as it changes over time.
  • Page 43 Manual 26043 723PLUS Performance Control ‘598’ The Available Trends are listed below, with the items they contain: Air Fuel Ratio  Air Manifold Pressure (Hg)  Air Manifold Pressure Reference (Hg)  Air Fuel Ratio Valve Demand %  Air Manifold Temperature (F) Ignition Timing ...
  • Page 44 723PLUS Performance Control ‘598’ Manual 26043 The axis provides another piece of information, the maximum and minimum value of its respective pen. This is indicated by two tic marks on the right side of the axis. When the program is first started, it initializes the values to 0, so it might be necessary to reset the Max and Min values once the program is running.
  • Page 45 Manual 26043 723PLUS Performance Control ‘598’ Log Status: This will show a dialog with estimated data rate values indicating how much physical data is being logged per second, per minute, and per hour. This is useful if you wish to have a log file kept for a longer period of time and want to make sure that you will not run out of disk space.
  • Page 46 723PLUS Performance Control ‘598’ Manual 26043 Pen X Minimum: This value is used in conjunction with Pen X Maximum. Pen X Maximum: This value and Pen X Minimum are used to scale the data in the graph window. Change these values to zoom in or out on a particular region for a given Pen.
  • Page 47: Hand Held Programmer And Menus

    Hand Held Programmer and Menus The Hand Held Programmer is a hand-held computer terminal that gets its power from the 723PLUS control. The terminal connects to the RS-422 communication serial port on the control (terminal J1). To connect the terminal, slightly loosen the right-hand screw in the cover over J1 and rotate the cover clockwise to expose the 9-pin connector.
  • Page 48 BKSP and SPACE keys will scroll through the display to show the remainder of a prompt if it is longer than the display screen's 19 characters. The 723PLUS has two sets of menus, the Service menus and the Configure menus. The Service menus allow easy access and tuning while the engine is running.
  • Page 49 (solid square) Not used. Displays the 723PLUS control part number and software revision level (can only be accessed from the TOP main screen). To return to menu header or to main screen, or to exit Configure and save set points.
  • Page 50: Configuration Menu Descriptions

    723PLUS Performance Control ‘598’ Manual 26043 Figure 3-1. Hand Held Programmer Functions Configuration Menu Descriptions CFIG Options USE NOTCH FILTER should be set TRUE to enable a notch filter on the speed input(s). Set FALSE to disable the notch filter.
  • Page 51 Manual 26043 723PLUS Performance Control ‘598’ USE TAC CONTROL should be set TRUE to bring into view the TURBO ASSIST SETPT menu and to enable Automatic Turbocharger Air Assist Control. Two methods of control are offered. For Discrete on/off control, Discrete Output #3 must be connected.
  • Page 52 723PLUS Performance Control ‘598’ Manual 26043 CFIG Speed Control RATED SPEED sets the rated engine speed in rpm. Refer to the engine nameplate for the engine speed rating. This sets the Rated Speed reference selected when the Idle/Rated input switch is closed.
  • Page 53 Manual 26043 723PLUS Performance Control ‘598’ TURBO # TEETH is the number of teeth or holes in the gear or slotted nut that the turbocharger speed sensor #2 is on. The control requires the number of teeth per turbocharger revolution.
  • Page 54 723PLUS Performance Control ‘598’ Manual 26043 SPEED #1 AND #2 FAIL sets the condition which will occur when a loss of both speed sensor #1 and #2 input signals has been detected. This condition may be enabled as a Shutdown, Alarm, or both by selecting TRUE in the appropriate menu.
  • Page 55 Manual 26043 723PLUS Performance Control ‘598’ CFIG Indication ON START FUEL LIMIT is set TRUE to display this fuel limit condition on the DISPLAY INDICATOR menu. Set FALSE to prevent display. ON MAX LIMIT is set TRUE to display this fuel limit condition on the DISPLAY INDICATOR menu.
  • Page 56 723PLUS Performance Control ‘598’ Manual 26043 11. HI AIR TEMP DELAY—Enter the delay time (in seconds) to wait before the HI AIR TEMP SD is issued after air manifold temperature exceeds the HI AIR TEMP SETPT. 12. ENERGIZE FOR SHDWN is set TRUE to energize Relay Output #1 with any shutdown condition.
  • Page 57 Manual 26043 723PLUS Performance Control ‘598’ 13. SHUTDOWN ACT ON ALM is set TRUE to shutdown the speed control fuel actuator with any alarm condition. Set FALSE to prevent shutdown of the speed control fuel actuator with any alarm condition.
  • Page 58 CFIG Communication The 723Plus has two serial ports that are configured to support the Modbus protocol. The ports are configured in this menu to set the slave address that they will use and to set if the port uses ASCII or RTU mode. Both ports have monitoring information available that can be retrieved by a Modbus master device such as a PC-based Human Machine Interface (HMI).
  • Page 59 At this time, we recommend saving the settings by pressing the “SAVE” key on the Hand Held Programmer or save settings using the 723PLUS Performance Control ‘598’ Control View or Watch Window (Refer to “help” if you need help).
  • Page 60: Service Menu Descriptions

    723PLUS Performance Control ‘598’ Manual 26043 Service Menu Descriptions Shutdown/Alarm These display menus are normally hidden and come into view when a shutdown or alarm condition exists. The display of first out status and faulted or normal condition of all configured shutdowns and alarms may then be viewed. Refer to the CFIG Shutdown/Alarms Menus for a listing of configurable shutdowns and alarms.
  • Page 61 Manual 26043 723PLUS Performance Control ‘598’ GAIN SLOPE BK PNT sets the percent output above which the Gain Slope becomes effective. It should usually be set just above the minimum load output. (See Figure 3-3.) GAIN SLOPE changes Gain as a function of actuator output. Since actuator output is proportional to engine load, this adjustment makes Gain a function of engine load.
  • Page 62: Figure 3-2. Control Gain As A Function Of Speed Error

    723PLUS Performance Control ‘598’ Manual 26043 Figure 3-2. Control Gain as a Function of Speed Error Figure 3-3. Control Gain as a Function of Control Output Woodward...
  • Page 63: Figure 3-4. Typical Transient Response Curves

    Manual 26043 723PLUS Performance Control ‘598’ Figure 3-4. Typical Transient Response Curves Woodward...
  • Page 64: Figure 3-5. Speed Filter

    723PLUS Performance Control ‘598’ Manual 26043 Figure 3-5. Speed Filter There are two adjustments—NOTCH FILT FREQ and NOTCH Q FACTOR. (See Figure 3-6.) Figure 3-6. Notch Filter Woodward...
  • Page 65 Manual 26043 723PLUS Performance Control ‘598’ 11. NOTCH FILT FREQ is the center frequency of rejection in Hertz. The notch filter is activated by setting USE NOTCH FILTER to TRUE in the CFIG Options menu. In tuning the notch filter, the resonant frequency must be identified and entered.
  • Page 66 723PLUS Performance Control ‘598’ Manual 26043 START SPEED is the initial speed reference for the speed control prior to starting. Start Speed must be set above cranking speed and below the speed achieved with the Start Fuel Limit setting (light-off speed). A ramp...
  • Page 67: Figure 3-7. Start Limit Function

    Manual 26043 723PLUS Performance Control ‘598’ Figure 3-7. Start Limit Function START RAMP RATE (%FD/sec) establishes the start limiter ramping rate at which the fuel demand increases to assist starting in colder ambient conditions. Set at 0.0 to disable the ramp function.
  • Page 68 723PLUS Performance Control ‘598’ Manual 26043 FGH READ VOLTS when TRUE changes the displayed AI1 Fuel Gas Header pressure to read Volts instead. AMT AI OFFSET adjusts the min displayed AI3 Air Manifold Temperature AMT AI SPAN adjusts the max displayed AI3 Air Manifold Temperature mA.
  • Page 69 Manual 26043 723PLUS Performance Control ‘598’ TORQUE LIMIT Curve Torque Limiter limits the fuel demand based on a two-dimensional curve and an engine speed input. This fuel limit prevents overfueling and limits torque for up to five speed breakpoints. The input breakpoints units are in rpm. The fuel limits are in percent fuel demand.
  • Page 70: Figure 3-8. Fuel Limit Breakpoints

    723PLUS Performance Control ‘598’ Manual 26043 Figure 3-8. Fuel Limit Breakpoints AFR Ctrl Dynamics AFRC GAIN determines how fast the control responds to an error in air manifold pressure from the air manifold pressure reference setting. The AFRC Gain is set to provide stable control of the air manifold pressure at all operating conditions.
  • Page 71 Manual 26043 723PLUS Performance Control ‘598’ AMP FILTER is a low-pass filter which is set to generate a delay in the Air Manifold pressure input to smooth out the signal by ignoring noise from the input. Default setting is 0.1. A lower setting will be more responsive but may be too unstable.
  • Page 72 723PLUS Performance Control ‘598’ Manual 26043 Set Analog Inputs This menu is provided to set the Analog Inputs engineering units. Be sure the units entered match the input sensing device calibration. REM SR @4mA EU (RPM)—Enter the preferred engine speed reference set point, in RPM, at 4 mA from the Remote Speed Reference input device.
  • Page 73 Comm Port Setup The 723Plus control has two serial ports that are configured to support the Modbus protocol. The ports are configured in this menu for the type of hardware interface and other parameters. Both ports have monitoring information available that can be retrieved by a Modbus master device such as a PC-based Human Machine Interface (HMI).
  • Page 74 PORT 2 TIMEOUT sets the time period, in seconds, the Modbus slave will wait for a master to query the 723PLUS. If the master connected to Port 2 does not poll within the timeout period, a configured MODBUS PORT 2 FAIL shutdown and/or alarm will be activated.
  • Page 75 10. PORT 3 TIMEOUT sets the time period, in seconds, the Modbus slave will wait for a master to query the 723PLUS. If the master connected to Port 3 does not poll within the timeout period, a configured MODBUS PORT 3 FAIL shutdown and/or alarm will be activated.
  • Page 76 723PLUS Performance Control ‘598’ Manual 26043 This 3D curve provides broad flexibility for mapping the air/fuel ratio as needed to achieve emission compliance and fuel economy over a wide range of speed and load combinations. Intermediate engine speeds (between Rated and Min Speed) produce intermediate air/fuel ratio settings.
  • Page 77 Manual 26043 723PLUS Performance Control ‘598’ 14 RESET ZERO R/L is provided to reset the raise/lower air manifold pressure bias adjustments back to zero. The control provides Raise/Lower air manifold pressure bias adjustments for temporarily increasing and decreasing air manifold pressure during site emission or fuel tests to readily determine the optimum air manifold pressure reference.
  • Page 78 723PLUS Performance Control ‘598’ Manual 26043 10. USE AMT BIAS—Set TRUE to apply an AMT bias of the Air/Fuel ratio setting. Set FALSE to disable an AMT bias of the Air/Fuel ratio setting. Ign Tmg Start Set This menu is used to set the Ignition Timing Starting curve (IGN_VS_AMP) and limits.
  • Page 79 Manual 26043 723PLUS Performance Control ‘598’ 10. AMP 4 TMG SET—Enter the ignition timing, in degrees (– = ATC, + = BTC), for the AMP 4 input level. 11. AMP 5 TMG SET—Enter the ignition timing, in degrees(– = ATC, + = BTC), for the AMP 5 input level.
  • Page 80 723PLUS Performance Control ‘598’ Manual 26043 FGH 2 RPM 2—Enter the Rated engine Speed (rpm) for setting the normal ignition timing high fuel gas header pressure input. Set same as FGH 1 RPM 2. FGH 1 RPM 1 TMG SET—Enter the Ignition Timing in degrees (+ = BTC, –...
  • Page 81 Manual 26043 723PLUS Performance Control ‘598’ 100% TQ ACT OUT—Enter the Actuator Output, Percent Fuel Demand, at Rated Speed, 100% Torque. MAX TQ ACT OUT—Enter the Actuator Output, Percent Fuel Demand, at Rated Speed, Maximum Ambient Torque. If engines are not Ambient Rated, set the MAX TQ ACT OUT at the 100% TQ ACT OUT setting.
  • Page 82 723PLUS Performance Control ‘598’ Manual 26043 TURBO ASSIST SET is the air manifold pressure reference, in inches mercury, for the Turbocharger Air Assist PID and where Discrete Output 3 is switched on when air manifold pressure is below this reference setting.
  • Page 83 Manual 26043 723PLUS Performance Control ‘598’ TC Module 1/4 This menu displays and allows calibration of LinkNet Thermocouple input Modules 1 through 4. The offset and span should be adjusted to produce the correct temperature display of the input temperature. The LinkNet Module must be connected and properly addressed for these menus to come into view.
  • Page 84 723PLUS Performance Control ‘598’ Manual 26043 AI “x” CH “x” - AI OFFSET sets the minimum value for the Channel “x” mA input current of the selected AI module. AI “x” CH “x” - AI SPAN sets the maximum value of the Channel “x” mA input current of the selected AI module.
  • Page 85 Manual 26043 723PLUS Performance Control ‘598’ PreComb Setting This menu is used to set the Pre-Combustion Chamber Pressure, in psi, from an Air Manifold Pressure versus Engine Speed curve. The output of this three- dimensional curve is the Pre-Combustion Chamber Pressure set point to the Pre- Combustion Chamber Pressure Analog Output 1 control.
  • Page 86 723PLUS Performance Control ‘598’ Manual 26043 14. PCC REF (0% Tq EU)—Enter the optimum pre-combustion pressure reference, in psi, for minimum speed, 0% torque operation. 15. LOAD IN (100% Tq EU)—Enter the air manifold pressure, in inches mercury, for minimum speed, 100% torque operation.
  • Page 87 Manual 26043 723PLUS Performance Control ‘598’ Display Analog I/O This menu is for display only. It displays the analog inputs and outputs of the 723PLUS control. SPD SENS IN #1 shows the frequency, in hertz, of the Speed Sensor #1 input signal.
  • Page 88 723PLUS Performance Control ‘598’ Manual 26043 Display IGN TMG This menu is for display only. It displays the Ignition Timing values and control modes. This menu comes into view when USE IGN TMG CTRL on the CFIG OPTIONS menu is configured TRUE. Otherwise, this menu is concealed.
  • Page 89 Manual 26043 723PLUS Performance Control ‘598’ REV AFR VLV DMND(%) shows the Air/Fuel Ratio valve demand, as percent travel, when reverse acting Air/Fuel Ratio control is configured. 0% travel is max air (exhaust bypass valve fully closed or air intake butterfly valve fully open).
  • Page 90 723PLUS Performance Control ‘598’ Manual 26043 SPEED SWITCH 1 will show TRUE when the Speed Switch 1 has been triggered. Display will show FALSE when the Speed Switch 1 is reset. SPEED SWITCH 2 will show TRUE when the Speed Switch 2 has been triggered.
  • Page 91 FORCE 723 DO This menu allows the 723PLUS Discrete Outputs to be manually forced on or off during installation to test the output loops. This feature and menu is only available when FORCE DISCRETE OUTS on the CFIG OPTION menu is set TRUE.
  • Page 92 723PLUS Performance Control ‘598’ Manual 26043 FORCE DO 1 This menu allows LinkNet Discrete Output 1 to be manually forced on or off during installation to test the output loops. This feature and menu is only available when FORCE DISCRETE OUTS on the CFIG OPTION menu is set TRUE.
  • Page 93: Chapter 4. Initial Adjustments

    Manual 26043 723PLUS Performance Control ‘598’ Chapter 4. Initial Adjustments Introduction This chapter contains information on control calibration. It includes initial prestart- up and start-up settings and adjustments. An improperly calibrated control could cause an engine overspeed or other damage to the engine. To prevent possible serious injury from an overspeeding engine, read this entire procedure before starting the engine.
  • Page 94: Speed Control Dynamic Adjustments

    This completes the start-up adjustments. We recommend saving the settings at this time by pressing the “SAVE” key on the Hand Held Programmer or by saving settings with the 723PLUS Performance Control ‘598’ Control View or Watch Window (Refer to “help” if you need help). The Programmer will display the message “Saving Changes”.
  • Page 95 Manual 26043 723PLUS Performance Control ‘598’  Min Gain is too low. If the preceding procedure does not improve the slow periodic cycling of the engine speed, the control may be limiting cycling through the low gain control region set by the Window Width set point.
  • Page 96: Air/Fuel Ratio Dynamic Adjustments

    723PLUS Performance Control ‘598’ Manual 26043 While operating at full load, record the Actuator Output on the Display Menu. Select the Maximum Fuel Limit set point on the Fuel Limiter Menu. Set at approximately 10% over the full load output if desired, otherwise leave at 100%.
  • Page 97: Speed Adjustments

    Manual 26043 723PLUS Performance Control ‘598’ If there is a slow periodic cycling of the air manifold pressure above and below the Turbo Assist Set reference, reduce the Turbo Assist Gain by 50% and increase Turbo Assist Reset slightly. Observe the movement of the Assist Air Demand output signal.
  • Page 98: Conclusion Of Setup Procedures

    Conclusion of Setup Procedures This completes the adjustment chapter. Save the set points by pressing the “SAVE” key on the Hand Held Programmer or save settings using the 723PLUS Performance Control ‘598’ Control View or Watch Window (Refer to “help” if you need help).
  • Page 99: Chapter 5. Description Of Operation

    Chapter 5. Description of Operation General This chapter provides an overview of the features and operation of the 723PLUS Digital Industrial Speed/Performance Control ‘598’. Figure 5-1 shows the control block diagram for reference in the following descriptions. The 723PLUS Digital Industrial Speed/Performance Control ‘598’ uses a 32-bit microprocessor for all control functions.
  • Page 100: Figure 5-1. Simplified Block Diagram

    723PLUS Performance Control ‘598’ Manual 26043 Figure 5-1. Simplified Block Diagram Woodward...
  • Page 101: Speed Control Dynamics

    Manual 26043 723PLUS Performance Control ‘598’ Speed Control Dynamics The control algorithms used in the 723PLUS Industrial Speed/Performance Control ‘598’ are designed specifically for reciprocating engine applications. The control offers an effective set of dynamics for variable speed, variable load operation.
  • Page 102: Maximum Fuel Function

    723PLUS Performance Control ‘598’ Manual 26043 Maximum Fuel Function The Maximum Fuel Function is a software-adjustable maximum fuel limit on the fuel demand. It is used to set a maximum position of the actuator. This is generally used to prevent engine overloading or other situations where the maximum fuel delivered to the engine should be limited.
  • Page 103: Fuel Limiting Function

    Manual 26043 723PLUS Performance Control ‘598’ Fuel Limiting Function Two separate Fuel Limiting Functions (AMP LIMIT curve and TORQUE LIMIT curve) provide limits to the fuel demand which prevents overfuel conditions. One function is based on an air manifold pressure transmitter signal provided at Signal Input #1.
  • Page 104: Alarm Reset

    Reset command. An Alarm Reset can be issued by Modbus Boolean Write (BW) address 0:0001. An Alarm Reset is also issued when power is applied to the 723PLUS. And finally, the control issues an Alarm Reset during start-up (when configured).
  • Page 105 Manual 26043 723PLUS Performance Control ‘598’ The idle speed set point is provided for engine start-up or cool down speed. Idle speed may be set equal to or less than the rated speed set point. Idle is independent of the lower limit set point and may be set to a lower speed. Idle speed cannot be changed except through adjustment of the idle speed set point.
  • Page 106: Air/Fuel Ratio Reference

    Air/Fuel Ratio Reference The 723PLUS control provides an Air/Fuel Ratio control reference, based on fuel gas header pressure, engine speed, and air manifold temperature inputs, and discrete inputs for temporarily raising and lowering the air manifold pressure reference.
  • Page 107 (or 20 to 4 mA when Reverse Acting is selected). The actuator normally controls a turbocharger exhaust bypass valve, an intake air throttle valve, or an air dump valve to regulate air manifold pressure. The 723PLUS A/F Ratio control is compatible with these valve types, with appropriate actuators, for all the configurations provided.
  • Page 108: Ignition Timing Reference

    Configuring an air manifold pressure input failed alarm or shutdown is recommended. Ignition Timing Reference The 723PLUS control provides three tunable ignition timing reference curves and one configurable starting ignition timing setting. Settings are also provided to limit maximum advance and maximum retard. A low signal selector determines which ignition timing signal is applied to the ignition timing output.
  • Page 109 Manual 26043 723PLUS Performance Control ‘598’ This 2D curve has five breakpoints for setting the ignition timing versus air manifold pressure. The ignition timing reference is linear between breakpoints. Normal Ignition Timing A three-dimensional curve sets the Normal Ignition Timing reference as a function of speed and load.
  • Page 110: Turbocharger Air Assist Control

    723PLUS Performance Control ‘598’ Manual 26043 Turbocharger Air Assist Control The 723PLUS control provides two choices for automatic turbocharger air assist control: Discrete relay Analog PID The choice is made by connecting to the preferred output type. Connection is not necessary if this function is not used by the application.
  • Page 111: Chapter 6. Troubleshooting

    The engine must be shut down for all system checks. Control Test and Calibration General Do the following checks on the 723PLUS control. Then verify the functioning of set points and adjustments. Connect the Hand Held Programmer, the 723PLUS Performance Control ‘598’...
  • Page 112 Failure indicates either the control or Hand Held Programmer (if applicable) has failed. If so, try this step with another Hand Held Programmer. If the test still fails, replace the 723PLUS control. If the test passes with the second Hand Held Programmer, replace the first Hand Held Programmer.
  • Page 113 AMT @4mA value set previously in the SET ANALOG INPUTS menu. If the meter indicates proper voltages (or currents) are present on Signal Input #3, but readings on the Hand Held Programmer, the 723PLUS Performance Control ‘598’ Control View or Watch Window are incorrect, the 723PLUS control is defective and should be replaced.
  • Page 114 ANALOG INPUTS menu. If the meter indicates proper voltages (or currents) are present on Signal Input #4, but readings on the Hand Held Programmer, the 723PLUS Performance Control ‘598’ Control View or Watch Window are incorrect, the 723PLUS control is defective and should be replaced.
  • Page 115: Conclusion Of Test And Calibration Procedures

    This completes the test and calibration chapter. Save the set points by pressing the “SAVE” key on the Hand Held Programmer, or save settings using the 723PLUS Performance Control ‘598’ Control View or Watch Window (refer to “help” if you need help). Power down the control for about 10 seconds. Restore power and verify that all set points are as recorded.
  • Page 116: Chapter 7. Product Support And Service Options

    A current list of Woodward Business Partners is available at www.woodward.com/directory. Product Service Options Depending on the type of product, the following options for servicing Woodward products may be available through your local Full-Service Distributor or the OEM or Packager of the equipment system.
  • Page 117: Returning Equipment For Repair

    To prevent damage to electronic components caused by improper handling, read and observe the precautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards, and Modules.
  • Page 118: Engineering Services

    Field Service engineering on-site support is available, depending on the product and location, from one of our Full-Service Distributors. The field engineers are experienced both on Woodward products as well as on much of the non- Woodward equipment with which our products interface.
  • Page 119: Technical Assistance

    723PLUS Performance Control ‘598’ Technical Assistance If you need to contact technical assistance, you will need to provide the following information. Please write it down here before contacting the Engine OEM, the Packager, a Woodward Business Partner, or the Woodward factory: General...
  • Page 120: Appendix A. Serial Communication Port Wiring

    RS-485 serial communications. The default settings are for RS-232. The RS-232 connections are shown in Figure A-1. The maximum distance from the master Modbus device to the 723PLUS control is 15 m (50 ft). Figure A-1. 723PLUS RS-232 Connections The RS-422 connections are shown in Figure A-2. The maximum distance from the master Modbus device to the 723PLUS control is 1219 m (4000 ft).
  • Page 121: Figure A-3. 723Plus Rs-485 Connections With Optional Termination

    723PLUS Performance Control ‘598’ The RS-485 connections are shown in Figure A-3. The maximum distance from the master Modbus device to the 723PLUS control is 1219 m (4000 ft). Figure A-3. 723PLUS RS-485 Connections with Optional Termination RS-422 and RS-485 can use a multi-drop set-up where more than one device is connected to a master device.
  • Page 122: Grounding And Shielding

    723PLUS Performance Control ‘598’ Manual 26043 Grounding and Shielding The RS-422 specifications state that a ground wire is needed if there is no other ground path between units. The preferred method to do this is to include a separate wire in the cable that connects the circuit grounds together. Connect the shield to earth ground at one point only.
  • Page 123: Appendix B. Linknet I/O Network

    An I/O network consists of the 723PLUS LON #1 channel, which provides independent network trunks of up to 9 I/O modules. The LinkNet I/O modules, or nodes, on each trunk are attached to the 723PLUS via a single twisted-pair wire (see end of this Appendix for correct wiring geometry).
  • Page 124: Figure B-1. Linknet Relay Contacts

    723PLUS Performance Control ‘598’ Manual 26043 Scan Rate Less than 7 output modules: (# of I/O modules x 6 + 75) ms typical (# of I/O modules x 6 + 100) ms max 7 or more output modules: (# of I/O modules x 6 + # of output modules x 3 + 55) ms typical...
  • Page 125: Individual I/O Module Specifications

    This address should correspond to the address of the I/O module hardware in the application program. If these rotary switches are set incorrectly, the node will not communicate with the 723PLUS, and a “no message” fault will be annunciated through the application program. If two nodes are set to the same address, an “address”...
  • Page 126: Figure B-2. Outline Drawing Of I/O Module

    723PLUS Performance Control ‘598’ Manual 26043 Figure B-2. Outline Drawing of I/O Module Woodward...
  • Page 127: Discrete Input Module

    Manual 26043 723PLUS Performance Control ‘598’ Discrete Input Module Figure B-3 is a block diagram and Figure B-4 is a wiring diagram of the Discrete Input module. The module receives information from field switches and relays. Power is provided for these contacts, on four terminal blocks, TB-5 through TB-8.
  • Page 128: Figure B-4. Discrete Input Module Wiring Diagram

    723PLUS Performance Control ‘598’ Manual 26043 Figure B-4. Discrete Input Module Wiring Diagram Woodward...
  • Page 129: 4-20 Ma Input Module

    0–5 V signal, and then multiplexed to a voltage-to-frequency converter. The module processor reads the period of this signal and converts it to a count, which it transmits through the transceiver to the 723PLUS. Figure B-5. 4–20 mA Input Module Block Diagram...
  • Page 130: Figure B-6. 4-20 Ma Input Module Wiring Diagram

    723PLUS Performance Control ‘598’ Manual 26043 Figure B-6. 4–20 mA Input Module Wiring Diagram Woodward...
  • Page 131: Thermocouple Input Module

    Each input is multiplexed to a voltage- to-frequency converter. The module processor reads the period of this signal and converts it to a count, which it transmits through the transceiver to the 723PLUS. Figure B-7. Thermocouple Input Module Block Diagram...
  • Page 132: Figure B-8. Thermocouple Input Module Wiring Diagram

    723PLUS Performance Control ‘598’ Manual 26043 Figure B-8. Thermocouple Input Module Wiring Diagram Woodward...
  • Page 133: Rtd Input Module

    The module processor reads the period of this signal and converts it to a count, which it transmits through the transceiver to the 723PLUS. Figure B-9. RTD Input Module Block Diagram...
  • Page 134: Figure B-10. Rtd Input Module Wiring Diagram

    723PLUS Performance Control ‘598’ Manual 26043 Figure B-10. RTD Input Module Wiring Diagram Woodward...
  • Page 135: Relay Output Module

    Output module. The module outputs information through eight 5 A form C relays. The relay output module processor receives information through the transceiver, from the 723PLUS. The node then updates the status of the shift register which updates the relays and a status LED. The second set of relay contacts is input back into the module processor through a shift register, for readback status.
  • Page 136: Figure B-12. Relay Output Module Wiring Diagram

    723PLUS Performance Control ‘598’ Manual 26043 Figure B-12. Relay Output Module Wiring Diagram Woodward...
  • Page 137: 4-20 Ma Output Module

    Figure B-13 is a block diagram and Figure B-14 is a wiring diagram of the 4–20 mA Output module. The 4–20 mA output module processor receives information through the transceiver, from the 723PLUS. The 4–20 mA output module then updates the status of the D/A converter which outputs voltages to the current drivers.
  • Page 138: Figure B-14. 4-20 Ma Output Module Wiring Diagram

    723PLUS Performance Control ‘598’ Manual 26043 Figure B-14. 4–20 mA Output Module Wiring Diagram Woodward...
  • Page 139: Figure B-15A. Troubleshooting Flowchart (1 Of 2)

    Manual 26043 723PLUS Performance Control ‘598’ Figure B-15a. Troubleshooting Flowchart (1 of 2) Woodward...
  • Page 140: Figure B-15B. Troubleshooting Flowchart (2 Of 2)

    723PLUS Performance Control ‘598’ Manual 26043 Figure B-15b. Troubleshooting Flowchart (2 of 2) Woodward...
  • Page 141: Troubleshooting Flowchart

    For optimum EMC performance, the network cable shield should be landed at each I/O module, and the exposed wire length limited to 25 mm (1 inch). At the 723PLUS, the outer insulation should be stripped and the bare shield landed to the chassis.
  • Page 142: Cable Length And Number Of Linknet I/O Modules

    723PLUS Performance Control ‘598’ Manual 26043 Correct cable is available from Woodward, Belden, or other suppliers providing an equivalent cable. Woodward part number 2008-349 Belden PO Box 1980 Richmond IN 47375 telephone (317) 983-5200 Belden Part Number Description 9207 PVC 20 AWG shielded. NEC Type CL2, CSA Cert. PCC FT 1.
  • Page 143: Appendix C. Modbus Slave Address Information

    Manual 26043 723PLUS Performance Control ‘598’ Appendix C. Modbus Slave Address Information Part Number 8280-598 This appendix contains the Modbus slave address information for 723PLUS part number 8280-598. MODBUS PORT2 Boolean Writes Addr Description 0:0001 ALARM RESET Boolean Reads Addr...
  • Page 144 723PLUS Performance Control ‘598’ Manual 26043 1:0044 1:0045 1:0046 1:0047 1:0048 1:0049 1:0050 1:0051 1:0052 1:0053 1:0054 1:0055 1:0056 1:0057 1:0058 1:0059 1:0060 1:0061 ALARM IS ACTIVE 1:0062 1-SPEED #1 FAIL ALARM 1:0063 2-SPEED #2 FAIL ALARM 1:0064 3-SPD #1 AND #2 FAIL ALARM...
  • Page 145 Manual 26043 723PLUS Performance Control ‘598’ 1:0108 SPEED SWITCH #1 ACTIVE 1:0109 SPEED SWITCH #2 ACTIVE 1:0110 AIR/FUEL RATIO IN CONTROL (LSS) 1:0111 ON A/F RATIO START LIMIT (LSS) 1:0112 ON A/F RATIO HI LIMIT (LSS) 1:0113 ON MIN AMP REF LIMIT (HSS)
  • Page 146 723PLUS Performance Control ‘598’ Manual 26043 3:0038 3:0039 3:0040 3:0041 AI1-AIR MANF PRESS (EU) 3:0042 A12-FUEL GAS HEADER PRESS (EU) 3:0043 AI3-AIR MANF TEMP (EU) 3:0044 AI4-REMOTE SPEED SETPOINT (RPM) 3:0045 AO1-CONFIGURED ANALOG OUTPUT(%EU X 10) 3:0046 AO2-OUTPUT TO IGN TIMER (%EU X 10)
  • Page 147 Manual 26043 723PLUS Performance Control ‘598’ MODBUS PORT3 Boolean Writes Addr Description 0:0001 ALARM RESET 0:0002 0:0003 0:0004 0:0005 0:0006 0:0007 0:0008 0:0009 0:0010 0:0011 USE RAISE SPEED REMOTE COMMAND 0:0012 USE LOWER SPEED REMOTE COMMAND 0:0013 USE RATED/IDLE REMOTE COMMAND...
  • Page 148 723PLUS Performance Control ‘598’ Manual 26043 1:0020 1:0021 SHUTDOWN IS ACTIVE 1:0022 1-SPEED #1FAIL SHUTDOWN 1:0023 2-SPEED #2 FAIL SHUTDOWN 1:0024 3-SPD #1 AND #2 FAIL SHUTDOWN 1:0025 4-AMP INPUT FAILED SHUTDOWN 1:0026 5-FGH INPUT FAILED SHUTDOWN 1:0027 6-AMT INPUT FAILED SHUTDOWN...
  • Page 149 Manual 26043 723PLUS Performance Control ‘598’ 1:0085 1:0086 1:0087 1:0088 1:0089 1:0090 1:0091 1:0092 1:0093 1:0094 1:0095 1:0096 1:0097 1:0098 1:0099 1:0100 1:0101 SPEED IN CONTROL (LSS) 1:0102 ON START LIMIT (LSS) 1:0103 ON MAX LIMIT (LSS) 1:0104 AT MIN FUEL (LSS)
  • Page 150 723PLUS Performance Control ‘598’ Manual 26043 3:0013 ENGINE SPEED (rpm) 3:0014 SPEED REFERENCE (rpm) 3:0015 FUEL DEMAND (%fd * 10) 3:0016 START FUEL LIMIT 3:0017 TORQUE LIMIT (%fd) 3:0018 AMP LIMIT (%fd) 3:0019 A/F RATIO PID REF (EU x 10)
  • Page 151 Manual 26043 723PLUS Performance Control ‘598’ 3:0082 TC 4 CHANNEL 4 (deg F) 3:0083 TC 4 CHANNEL 5 (deg F) 3:0084 TC 4 CHANNEL 6 (deg F) 3:0085 RTD 1 CHANNEL 1 (deg F) 3:0086 RTD 1 CHANNEL 2 (deg F)
  • Page 152: Appendix D. Programming Checklist

    723PLUS Performance Control ‘598’ Manual 26043 Appendix D. Programming Checklist We recommend you write down the final value of each menu item here so you will have a record if you later need to reprogram or replace the control. From the Hand Held Programmer Main Menu Header press ‘ID’, or from Watch Window or Control View select “Help About”, to get the Software Part Number...
  • Page 153 Manual 26043 723PLUS Performance Control ‘598’ CFIG SHUTDOWNS Default SPEED #1 FAIL #FALSE SPEED #2 FAIL #FALSE SPD #1 AND #2 FAIL #FALSE AMP INPUT FAILED #FALSE FGH INPUT FAILED #FALSE AMT INPUT FAILED #FALSE REM INPUT FAILED #FALSE MODBUS PORT2 FAIL...
  • Page 154 723PLUS Performance Control ‘598’ Manual 26043 ALARM SETUP Default (Low, High) HI FUEL DEMND SETPT(%FD) #100.0 (0.0, 100.0) HI FUEL DEMND DELAY(SEC) #10.0 (0.0, 10800.0) HI SPEED SETPOINT (RPM) #1320.0 (0.0, 2500.0) HI SPEED DELAY(SEC) #0.2 (0.0, 10800.0) STALL SETPOINT(RPM) #25.0 (0.0, 100.0)
  • Page 155 Manual 26043 723PLUS Performance Control ‘598’ Service Menus SHUTDOWN MENU Default Field Setting FIRST SHUTDOWN 1-SPEED #1FAIL 2-SPEED #2 FAIL 3-SPD #1AND#2 FAIL 4-AMP INPUT FAILED 5-FGH INPUT FAILED 6-AMT INPUT FAILED 7-REM INPUT FAILED 8-MODBUS 2 FAIL 9-MODBUS 3 FAIL...
  • Page 156 723PLUS Performance Control ‘598’ Manual 26043 SPEED SETTING Default (Low, High) RAISE SPEED LIMIT (RPM) *330 (1, 2100) LOWER SPEED LIMIT (RPM) *198 (1, 2100) IDLE SPEED (RPM) *220 (1, 2100) START SPEED (RPM) *125 (1, 2100) START TIME (SEC) *14.0 (0.0, 60.0)
  • Page 157 Manual 26043 723PLUS Performance Control ‘598’ TORQUE LIMIT CURVE Default (Low, High) ENABLE TORQUE LIMIT *FALSE TORQUE LMT BRKPNT A(RPM) *198.0 (0.0, 1600.0) FUEL LMT @ BRKPNT A (%FD) *100.0 (0.0, 100.0) TORQUE LMT BRKPNT B(RPM) *231.0 (0.0, 1600.0) FUEL LMT @ BRKPNT B (%FD) *100.0 (0.0, 100.0)
  • Page 158 723PLUS Performance Control ‘598’ Manual 26043 SET ANALOG OUTPUTS Default (Low, High) ANALOG OUTPUT 1 MIN(EU) *0.0 (-32767.0, 32767.0) ANALOG OUTPUT 1 MAX(EU) *330.0 (-32767.0, 32767.0) ANALOG OUTPUT 2 MIN(EU) *-32.0 (-36.0, 45.0) ANALOG OUTPUT 2 MAX(EU) *4.0 (0.0, 45.0) ANALOG OUTPUT 4 MIN (%) *0.0 (-20.0, 135.0)
  • Page 159 Manual 26043 723PLUS Performance Control ‘598’ IGN TMG START SET Default (Low, High) MAX RETARD LMT(DEG) *-25.0 (-40.0, 45.0) AMP 1 (in Hg) *0.0 (-0.1, 0.0) AMP 2 (in Hg) *5.0 (0.0, 50.0) AMP 3 (in Hg) *7.0 (0.0, 50.0) AMP 4 (in Hg) *40.0 (0.0, 50.0)
  • Page 160 723PLUS Performance Control ‘598’ Manual 26043 TC MODULE 1 Default (Low, High) CH1 - TC DEGREES F CH2 - TC DEGREES F CH3 - TC DEGREES F CH4 - TC DEGREES F CH5 - TC DEGREES F CH6 - TC DEGREES F CH1 - TC OFFSET *0.0 (-500.0, 500.0)
  • Page 161 Manual 26043 723PLUS Performance Control ‘598’ TC MODULE 3 Default (Low, High) CH1 - TC DEGREES F CH2 - TC DEGREES F CH3 - TC DEGREES F CH4 - TC DEGREES F CH5 - TC DEGREES F CH6 - TC DEGREES F CH1 - TC OFFSET *0.0 (-500.0, 500.0)
  • Page 162 723PLUS Performance Control ‘598’ Manual 26043 RTD MODULE 1 Default (Low, High) CH1 - RTD DEGREES F CH2 - RTD DEGREES F CH3 - RTD DEGREES F CH4 - RTD DEGREES F CH5 - RTD DEGREES F CH6 - RTD DEGREES F CH1 - RTD OFFSET *0.0 (-500.0, 500.0)
  • Page 163 Manual 26043 723PLUS Performance Control ‘598’ DI MODULE 1 Display Only CH01 CONTACT CLOSED CH02 CONTACT CLOSED CH03 CONTACT CLOSED CH04 CONTACT CLOSED CH05 CONTACT CLOSED CH06 CONTACT CLOSED CH07 CONTACT CLOSED CH08 CONTACT CLOSED CH09 CONTACT CLOSED CH10 CONTACT CLOSED...
  • Page 164 723PLUS Performance Control ‘598’ Manual 26043 PRECOMB SETTING Default (Low, High) RATED SPEED CURVE (RPM) *330.0 (0.0, 2100.0) PCC REF (RS,100%TQ EU) *40.0 (0.0, 100.0) PCC REF (RS,75%TQ EU) *25.0 (0.0, 100.0) PCC REF (RS,50%TQ EU) *10.0 (0.0, 100.0) PCC REF (RS,0%TQ EU) *5.0 (0.0, 100.0)
  • Page 165 Manual 26043 723PLUS Performance Control ‘598’ DISPLAY AMP AFR Display Only AIR MANF PRESS (in Hg) AIR MANF PR REF (in Hg) AFR VLV DEMAND(%) REV AFR VLV DMND(%) IN A/F CONTROL (LSS) ON DFLT A/F RATIO ON MIN AIR LIMIT...
  • Page 166 723PLUS Performance Control ‘598’ Manual 26043 FORCE DO 1 Default DO1 CH1 FORCE *FALSE DO1 CH2 FORCE *FALSE DO1 CH3 FORCE *FALSE DO1 CH4 FORCE *FALSE DO1 CH5 FORCE *FALSE DO1 CH6 FORCE *FALSE DO1 CH7 FORCE *FALSE DO1 CH8 FORCE...
  • Page 167: 723Plus Control Specifications

    723PLUS Control Specifications Woodward Part Numbers: 8280-598 723PLUS with low-voltage power supply 9907-205 Hand Held Programmer 8923-932 Watch Window Installation 8928-060 Standard Performance Control ‘598’ PC Interface Installation Power Supply Rating 18–40 Vdc (24 or 32 Vdc nominal) Power Consumption...
  • Page 168 Email and Website—www.woodward.com Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address / phone / fax / email information for all locations is available on our website.

Table of Contents