12 OVERSPEED (*T/F)—Set this value "FALSE" if no major alarm output is
desired when engine overspeed occurs. Set this value "TRUE" if a major alarm
output is desired when engine overspeed occurs.
13 CLUTCH FAIL (*T/F)—Set this value "FALSE" if no major alarm output is
desired when a clutch engaged contact is not received within the CLUTCH SYNC
TIME. Set this value "TRUE" if a major alarm is desired when the clutch engaged
contact is not received within the CLUTCH SYNC TIME.
14 ACTUATOR MODE (MECH GOV) (*T/F)—Set this value "FALSE" if no major
alarm output is desired when the ACTUATOR MODE discrete input contact is
open. Set this value "TRUE" if a major alarm is desired when the ACTUATOR
MODE discrete input contact is closed.
15 TORQ DEV ERROR (*T/F)—Set this value "FALSE" if no major alarm output
is desired when a TORQUE DEVIATION is sensed. Set the value "TRUE" if a
major alarm is desired.
D**CONFIG MINOR ALARMS**
Enabling any one or a combination of the following alarms is acceptable as they
are linked together as logical "ORs". This is relay output #1, 723PLUS control
terminals #3 and #4. The output goes to the TANO panel and will alarm a Minor
Governor Alarm when energized.
01 MPU 1 FAILED (*T/F)—Set this value "FALSE" if failure of MPU 1 input is not
to be a minor alarm. Set this value "TRUE" if failure of MPU 1 input is to be
alarmed as a minor alarm.
02 MPU 2 FAILED (*T/F)—Set this value "FALSE" if failure of MPU 2 input is not
to be a minor alarm. Set this value "TRUE" if failure of MPU 2 input is to be
alarmed as a minor alarm.
03 REMOTE SPEED FAILED (*T/F)—Set this value "FALSE" if failure of Remote
Speed Setting input is not to be a minor alarm. Set this value "TRUE" if failure of
Remote Speed Setting input is to be alarmed as a minor alarm.
04 TORQUE INPUT FAILED (*T/F)—Set this value "FALSE" if failure of the
TORQUE input is not to be a minor alarm. Set this value "TRUE" if failure of
TORQUE input is to be alarmed as a minor alarm.
05 RACK POSN INPUT FAILED (*T/F)—Set this value "FALSE" if failure of the
rack position input is not to be a minor alarm. Set this value "TRUE" if failure of
the rack position input is to be alarmed as a minor alarm.
06 HIGH ACT ALARM (*T/F)—Set this value "FALSE" if no minor alarm output is
desired when Maximum Fuel Limiter is in control (limiting) of the actuator driver
output. Set this value "TRUE" if a minor alarm output is desired when Maximum
Fuel Limiter is in control (limiting) of the actuator driver output.
07 CLON CH1 ERROR (*T/F)—Set this value "FALSE" if no minor alarm output
is desired when a Control LON Channel 1 error is detected. Set this value
"TRUE" if a minor alarm output is desired when a Control LON Channel 1 error is
detected.