Page 1
Installation and Operation Manual L-Series Position Controller Manual 26237 (Revision F)
Page 2
Revisions—Text changes are indicated by a black line alongside the text. Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken.
PTIONS Product Service Options ..................51 Returning Equipment for Repair ................52 Replacement Parts ....................53 How to Contact Woodward ................... 53 Engineering Services .................... 54 Technical Assistance .................... 55 A. A ..........56 ...
L-Series Position Controller Regulatory Compliance The L-Series is suitable for use in Class I, Division 2, Groups A, B, C, D per CSA for Canada and U.S. or non-hazardous locations only. Wiring must be in accordance with North American Class I, Division 2 wiring methods as applicable, and in accordance with the authority having jurisdiction.
PCB from the control cabinet, place it in the antistatic protective bag. CAUTION—ELECTROSTATIC DISCHARGE To prevent damage to electronic components caused by improper handling, read and observe the precautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards, and Modules. Woodward...
OEMs themselves may find it useful to copy some of the information from this manual into their application user manuals. How to Use This Manual The following summarizes how to install a L-Series actuator into a new or existing system: •...
More detail on the features of the L-Series can be found later in this manual. WARNING—EMERGENCY STOP When included with an ITB, the actuator depends solely on the return spring...
Manual 26237 L-Series Position Controller Service Tool Software The L-Series Service Tool software is a Microsoft Windows based GUI (graphic user interface). The Service Tool Software is compatible with Windows 95/98/NT/00 and gives the OEM the ability to: • Configure product settings based on application requirements •...
Service Tool Driver Input Power The L-Series will handle a voltage range of 10 to 28 Vdc at full specified torque. The actuator is functional in the range of 8 to 32 Vdc, but accuracy and/or torque can be diminished at the extreme ends of this range.
Page 11
Run Enable (optional) Position Command Signal The L-Series can accept either a PWM command signal input or an analog 0–5 Vdc command signal input, depending on how the software application is configured. The PWM will function with various types of input sources, including high-side, low-side open collector, and push-pull—depending on the configuration.
L-Series Position Controller Manual 26237 user-defined shutdown failsafe direction user-defined shutdown failsafe direction PWM Position Signal Duty Cycle, % Figure 2-1. PWM Linear Demand to Position user-defined shutdown failsafe direction user-defined points PWM Position Signal Duty Cycle, % Figure 2-2. PWM Non-Linear Demand to Position The 0–5 V input uses a different pin in the connector, and it has a usable range...
Manual 26237 L-Series Position Controller user-defined shutdown failsafe direction user-defined shutdown failsafe direction Position Signal Voltage Figure 2-3. Analog 0–5 V Linear Demand to Position user-defined shutdown failsafe direction user-defined points Position Signal Voltage Figure 2-4. Analog 0–5 V Non-Linear Demand to Position Discrete Output A discrete output is provided to serve as a status indicator.
Chapter 3 (Installation). 5V Output—A 5 Vdc output has been provided on the L-Series actuator to power external sensors, if necessary. The 5 V output is limited to 10 mA, but this is sufficient for most light-duty ratiometric sensors.
The service port is provided for configuration and setup only. Temperature Sensing The L-Series has an on-board temperature sensor to monitor board temperatures and protect the unit from overtemperature. This temperature is monitored and a fault is annunciated if the set point is exceeded.
Page 16
L-Series Position Controller Manual 26237 Brownout Reset Brownout Reset is true if CPU Voltage drops below 4.2 V but not below 1 V. The brownout detect circuit will reset the CPU. This is a hard-coded alarm. If detected, the control will attempt to continue normal operation.
Page 17
Manual 26237 L-Series Position Controller Can be configured as an alarm or shutdown. If configured as a shutdown, the control will go limp if this fault is detected. If configured as an alarm, the control will attempt to continue normal operation if this fault is detected.
Page 18
L-Series Position Controller Manual 26237 Run Enable Shutdown Run Enable discrete input is opened, only active when this input is configured for use. This is a hard-coded shutdown. The control will go limp if this condition is detected. Woodward...
L-Series Position Controller Chapter 3. Installation Introduction This chapter provides instructions on how to mount and connect the L-Series controller into a system. Hardware dimensions are provided for mounting the device to a specific application. WARNING—NOISE Due to typical noise levels in turbine or engine environments, hearing protection should be worn when working on or around the L-Series.
The operating temperature range of the control is –40 to +105 °C (–40 to +221 °F). In spark-ignited applications, make sure the L-Series is located away from the ignition coil, and that harness wires are not routed next to the spark plug wires.
L-Series Position Controller Figure 3-3c. L-Series Shaft Types Electrical Installation A wiring pinout of the L-Series control, as viewed by looking into the control’s connector feature, is shown in Figure 3-4. Typical connections to external devices are also shown. Woodward...
Page 26
L-Series Position Controller Manual 26237 The L-Series has an operating voltage range of 8 to 32 Vdc with nominal voltages of 12 or 24 Vdc. The power supply is reverse polarity protected, and consumes 32 W maximum power at a peak current of 1 A (32 V) assuming 4 Ω...
Representative circuitry for the L-Series inputs/outputs is provided in Figure 3-5 below. Power Supply Input (+12 Vdc/24 Vdc at pin 1, ground at pin 5)—The L-Series is configured for 12 or 24 V nominal operation, although it will handle 8–32 V. The...
Page 28
Woodward recommends using a 6 A slow-blow fuse on the power supply line feeding pin 1 of the L-Series actuator. WARNING—FUSED INPUT POWER The input power must be fused. Failure to fuse the L-Series could, under exceptional circumstances, lead to personal injury, damage to the control valve, and/or explosion.
By default, this circuit will be configured in a failsafe manner, meaning it will be active (conducting) when no fault exists, but if power is lost or a fault is detected by the L-Series actuator, the circuit will open. See Figure 3-6 below for typical usage of this feature.
0.5V to 4.5VDC Processor Command Signal 1000pF 499k ** if optional external Run Enable is chosen during L-Series configuration, Aux. 1 can be used to enable or disable the actuator output shaft torque. Figure 3-7. Typical AUX1 and AUX2 Usage Woodward...
THERE IS NOT AN INTERNAL CONNECTION TO CIRCUIT GROUND. Terminal pins 3 and 5 must be used for access to the circuit ground. This junction point is completely electrically isolated from the L-Series actuator’s electronics, and is solely for convenience during installation.
Service Tool Introduction This chapter covers the process of tuning, configuring, calibrating, and servicing the control via the L-Series Service Tool. It is assumed that the control has already been installed on the engine. NOTE Many applications are delivered pre-configured, calibrated, and tuned. These units do not require the use of the Service Tool.
CAUTION—SERIAL PORT DAMAGE POTENTIAL There is a potential for serial port damage when communicating with the L-Series control. This is caused by a difference in ac voltage between neutral and earth ground. If the PC RS-232 port ground is referenced to ac neutral, and the L-Series control is referenced to battery ground (ac earth ground), a large amount of current can be experienced.
What to do next After the software is installed, connect a serial communications cable between the RS-232 connections on the L-Series control and an unused serial port on your computer. Run the Service Tool program and select the appropriate comm port.
Software Version Identification The Service Tool software version can found by selecting ‘About’ under the Help menu. The L-Series software version can be found on the right-most tab sheet (Identification) of the Service Tool screen. The Service Tool and Control must be connected to view this information.
Manual 26237 L-Series Position Controller Configuring the Unit—Off-Line Unit configuration is summarized as follows: • Open the Configuration Editor Dialog using the File/New or File/Open options. • Edit the configuration settings. • Save the configuration to a file. At a later date simply open the configuration and load it into the control.
L-Series Position Controller Manual 26237 Figure 4-4. Configuration Editor—Analog Settings Proportional Gain Sets the position controller PID’s proportional gain. Increased gain corresponds to increased PID output (higher proportional = faster response). This setting can also be dynamically adjusted using the PID Tuning screen. Allowed values: 0–...
Page 39
PWM (see Figure 4-5). PWM Pull Up Select Selects the appropriate PWM source. This configures the L-Series input internally to provide the proper pull-up logic. For details on selection of this parameter, refer to Chapter 3. Allowed values: Push-Pull, High Side Drive, or Low Side Drive.
L-Series Position Controller Manual 26237 Figure 4-5. Configuration Editor—PWM Settings Discrete Output Tab Sheet This screen contains the discrete output configuration settings. If the discrete output is not used, then these settings can be skipped. Relay Output Configuration The relay output can be configured to one of the following:...
Manual 26237 L-Series Position Controller Figure 4-6. Configuration Editor—Discrete Output Settings Alarm/Shutdown Tab Sheet This screen contains the alarm and shutdown configuration settings. Shutdown/Alarm Fault Selections The list of faults displayed can be individually selected to either perform a Shutdown or just Alarm (no action).
L-Series Position Controller Manual 26237 Figure 4-7. Configuration Editor—Alarm/Shutdown Settings Loading the Configuration (Save) Select the File/Load to Control from the menu or Blue Arrow icon on the Configuration Editor to load the changes into the control. Monitoring the Driver The Service Tool has five different tab sheets to monitor driver parameters.
L-Series Position Controller Communication Status This section of the status bar shows the status of communication between the service tool and the L-Series Driver. For more information, see Establishing Communication. • Connected—The Service Tool is connected to and communicating with the driver.
Page 44
L-Series Position Controller Manual 26237 Supply Voltage Displayed value of the input power, in volts, as read by the processor. Power Demand Displayed value of the power demanded, in watts, as read by the processor. This is an indication of the work output.
Latched faults can be cleared by cycling power on the L-Series control or by selecting the ‘Reset Alarms and Shutdowns’ button on any of the Alarm or Shutdown screens.
To get to the PID Tuning screen, select the Edit Position PID from the Tools menu selection. The L-Series controller can be put into a manual control mode from this screen by selecting the “Enable Manual Position Tuning’ checkbox (Figure 4-13). Once in manual mode, the position setpoint box is highlighted and the value displayed is actively positioning the output.
L-Series Position Controller Manual 26237 Figure 4-13. Service Tool—PID Tuning Window Figure 4-14. Service Tool—PID Tuning Properties Window Position Calibration and Verification Position calibration is available to map the position command input to the actual rotational travel of the unit. It is only used when the full travel of the actuator is constrained or limited such that 0 to 60 degrees of travel is not used.
1. Select Automatic Position Calibration Mode. 2. Select cw or ccw Direction. 3. L-Series automatically rotates in both cw and ccw directions until the stops are detected. The values are then captured and stored. 4. When completed, cycle the power on the L-Series.
L-Series Position Controller Manual 26237 The Full Travel Actual Position is the full stroke factory position without user stops after software linearization. The Full Travel Sensor Position is the full stroke factory position without user stops before software linearization. The Full Travel Sensor Position will match the TPS Output Signal.
Manual 26237 L-Series Position Controller Figure 4-16. Service Tool—Manual Position Calibration The next screen is used to set the minimum and maximum positions for the user soft stops. To find the minimum and maximum soft stops use the verify position mode described above to position the valve and use the Full Travel Actual Position reading for minimum and maximum position values.
L-Series Position Controller Manual 26237 Automatic The automatic calibration mode is used to set the minimum position and fail direction and to calibrate the valve to user physical stops (mechanical hard stops). Like the manual mode, the first screen to appear is used to set the minimum position and fail direction.
For more detailed information about governor system failure modes and effects, contact Woodward for a copy of the system DFMEA. The troubleshooting scenarios listed below assume that the end user has a digital multimeter at his disposal for testing voltages and checking continuity, and assume that the application has been engineered and tested thoroughly.
L-Series Position Controller Manual 26237 Engine/Generator Troubleshooting Problem Possible Cause Suggested Test/Correction Engine does not Stuck throttle/frozen shaft Move throttle by hand. Assess start smoothness, friction, and return spring force. Power not applied to control Disconnect starter motor solenoid. Disconnect harness from governor.
Page 55
Verify the port setting is correct. Service Tool not Old version of Service Tool Re-install Service Tool, get the latest communicating– or file corruption or bad version from the Woodward web site ‘Error message install. (www.woodward.com) displayed on PC when trying to...
Verify the input is properly configured. Alarm or Shutdown Conditions If the L-Series control has any alarm or shutdown conditions, refer to Chapter 2 for details on the exact cause of the condition. The Service Tool must be used to determine the cause of any shutdown or alarm condition.
Product Service Options The following factory options are available for servicing Woodward equipment, based on the standard Woodward Product and Service Warranty (5-01-1205) that is in effect at the time the product is purchased from Woodward or the service is performed: •...
Returning Equipment for Repair If a control (or any part of an electronic control) is to be returned to Woodward for repair, please contact Woodward in advance to obtain a Return Authorization Number. When shipping the item(s), attach a tag with the following information: •...
To expedite the repair process, contact Woodward in advance to obtain a Return Authorization Number, and arrange for issue of a purchase order for the item(s) to be repaired. No work can be started until a purchase order is received.
L-Series Position Controller Manual 26237 Engineering Services Woodward Industrial Controls Engineering Services offers the following after- sales support for Woodward products. For these services, you can contact us by telephone, by email, or through the Woodward website. • Technical Support •...
Type of Fuel (gas, gaseous, steam, etc) Rating Application Control/Governor Information Please list all Woodward governors, actuators, and electronic controls in your system: Woodward Part Number and Revision Letter Control Description or Governor Type Serial Number Woodward Part Number and Revision Letter...
Isoch isochronous integrated throttle body L-Series Woodward electronic engine governor that contains both a rotary actuator and a controller circuit board magnetic pick up original equipment manufacturer pulse-width modulated revolutions per minute RS-232 a communications standard...
Manual 26237 L-Series Position Controller Appendix B. L-Series Configuration Summary APPLICATION ________________________________________________ ACTUATOR SERIAL NUMBER ____________________________________ For details on individual settings, refer to Chapter 4. Configuration Settings – Position Controller Setup Position Demand Selection PWM ____ 0..5 V ____ Fail Direction...
L-Series Position Controller Manual 26237 Appendix C. L-Series Control Specifications Specifications Power Supply 12/24 V systems (10–32 Vdc) reverse polarity protection, 2.5 A max Power Consumption 32 W maximum Torque Nominal: 0.34 N m (0.25 lb-ft) Minimum Transient (up to 105 °C): 0.28 N m (0.21 lb-ft)
Page 65
Reliability and Quality Goals The L-Series control system has a reliability target of 17 500 hours MTBF. It also has a quality goal of less than 25 PPM when measuring out-of-the-box defects. This quality goal is a target based on continuous improvement.
Page 66
L-Series Position Controller Manual 26237 Discrete Input Parameter Value Input Current 0.5 mA @ 5 Vdc Input Type Ground referenced discrete input Delay Time for Shutdown < 200 ms for system to recognize shutdown Delay Time for Reset < 1 s for valves to move to minimum position...
Position Demand Algorithms 6.5 ms Analog Input Logic 6.5 ms PWM Input Logic 6.5 ms Serial Port background task Run Enable Discrete Input 6.5 ms Discrete Output 6.5 ms Diagnostics 6.5 ms Figure C-1. Bode Plot of L-Series Response Woodward...
Page 70
Phone +1 (970) 482-5811 • Fax +1 (970) 498-3058 Email and Website—www.woodward.com Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address / phone / fax / email information for all locations is available on our website.