Information List - Siemens 7SK80 Manual

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Addr.
Parameter
8105
BAL. FACTOR I
Σ I THRESHOLD
8106
Σ I FACTOR
8107
FAST Σ i MONIT
8109
8110A
T BAL. V LIMIT
8111A
T BAL. I LIMIT

2.10.1.9 Information List

No.
Information
161
Fail I Superv.
Failure Σ I
162
163
Fail I balance
167
Fail V balance
169
VT FuseFail>10s
170
VT FuseFail
171
Fail Ph. Seq.
175
Fail Ph. Seq. I
176
Fail Ph. Seq. V
197
MeasSup OFF
253
VT brk. wire
255
Fail VT circuit
256
VT b.w. 1 pole
257
VT b.w. 2 pole
258
VT b.w. 3 pole
6509
>FAIL:FEEDER VT
6510
>FAIL: BUS VT
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
C
Setting Options
0.10 .. 0.90
0.05 .. 2.00 A; ∞
1A
0.25 .. 10.00 A; ∞
5A
0.00 .. 0.95
OFF
ON
0 .. 100 sec
0 .. 100 sec
Type of In-
formation
OUT
Failure: General Current Supervision
OUT
Failure: Current Summation
OUT
Failure: Current Balance
OUT
Failure: Voltage Balance
OUT
VT Fuse Failure (alarm >10s)
OUT
VT Fuse Failure (alarm instantaneous)
OUT
Failure: Phase Sequence
OUT
Failure: Phase Sequence Current
OUT
Failure: Phase Sequence Voltage
OUT
Measurement Supervision is switched OFF
OUT
Failure VT circuit: broken wire
OUT
Failure VT circuit
OUT
Failure VT circuit: 1 pole broken wire
OUT
Failure VT circuit: 2 pole broken wire
OUT
Failure VT circuit: 3 pole broken wire
SP
>Failure: Feeder VT
SP
>Failure: Busbar VT
Default Setting
0.50
Balance Factor for Current
Monitor
0.10 A
Summated Current Moni-
toring Threshold
0.50 A
0.10
Summated Current Moni-
toring Factor
ON
Fast Summated Current
Monitoring
5 sec
T Balance Factor for
Voltage Monitor
5 sec
T Current Balance Monitor
Comments
Functions
2.10 Monitoring Functions
Comments
177