Siemens 7SK80 Manual page 464

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Appendix
A.8 Settings
Addr.
Parameter
4105
STARTUP T WARM
4106
TEMP.COLD MOTOR
4201
FCT 49
4202
49 K-FACTOR
4203
TIME CONSTANT
49 Θ ALARM
4204
4205
I ALARM
4207A
Kτ-FACTOR
4208A
T EMERGENCY
4209
49 TEMP. RISE I
4210
49 TEMP. RISE I
4301
FCT 66
4302
IStart/IMOTnom
4303
T START MAX
4304
T Equal
4305
I MOTOR NOMINAL
4306
MAX.WARM STARTS
4307
#COLD-#WARM
4308
Kτ at STOP
4309
Kτ at RUNNING
4310
T MIN. INHIBIT
4311
ROTOR OVERLOAD
4401
Load Jam Prot.
4402
Load Jam I>
4403
TRIP DELAY
4404
I Alarm
4405
ALARM DELAY
4406
T Start Blk.
5001
FCT 59
5002
59-1 PICKUP
5003
59-1 PICKUP
5004
59-1 DELAY
5005
59-2 PICKUP
5006
59-2 PICKUP
5007
59-2 DELAY
5015
59-1 PICKUP V2
5016
59-2 PICKUP V2
5017A
59-1 DOUT RATIO
5018A
59-2 DOUT RATIO
464
Function
C
0.5 .. 180.0 sec; ∞
48/66/51M Motor
0 .. 80 %; ∞
48/66/51M Motor
49 Th.Overload
OFF
ON
Alarm Only
49 Th.Overload
0.10 .. 4.00
49 Th.Overload
1.0 .. 999.9 min
49 Th.Overload
50 .. 100 %
49 Th.Overload
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
49 Th.Overload
1.0 .. 10.0
49 Th.Overload
10 .. 15000 sec
49 Th.Overload
40 .. 200 °C
49 Th.Overload
104 .. 392 °F
48/66/51M Motor
OFF
ON
48/66/51M Motor
1.10 .. 10.00
48/66/51M Motor
1 .. 320 sec
48/66/51M Motor
0.0 .. 320.0 min
48/66/51M Motor
1A
0.20 .. 1.20 A
5A
1.00 .. 6.00 A
48/66/51M Motor
1 .. 4
48/66/51M Motor
1 .. 2
48/66/51M Motor
0.2 .. 100.0
48/66/51M Motor
0.2 .. 100.0
48/66/51M Motor
0.2 .. 120.0 min
48/66/51M Motor
ON
OFF
Alarm Only
48/66/51M Motor
OFF
ON
Alarm Only
48/66/51M Motor
1A
0.50 .. 12.00 A
5A
2.50 .. 60.00 A
48/66/51M Motor
0.00 .. 600.00 sec
48/66/51M Motor
1A
0.50 .. 12.00 A
5A
2.50 .. 60.00 A
48/66/51M Motor
0.00 .. 600.00 sec
48/66/51M Motor
0.00 .. 600.00 sec
27/59 O/U Volt.
OFF
ON
Alarm Only
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
2 .. 150 V
27/59 O/U Volt.
2 .. 150 V
27/59 O/U Volt.
0.90 .. 0.99
27/59 O/U Volt.
0.90 .. 0.99
Setting Options
Default Setting
10.0 sec
25 %
OFF
1.10
100.0 min
90 %
1.00 A
5.00 A
1.0
100 sec
100 °C
212 °F
OFF
4.90
10 sec
1.0 min
1.00 A
5.00 A
2
1
5.0
2.0
6.0 min
ON
OFF
2.00 A
10.00 A
1.00 sec
1.80 A
9.00 A
1.00 sec
10.00 sec
OFF
110 V
110 V
0.50 sec
120 V
120 V
0.50 sec
30 V
50 V
0.95
0.95
E50417-G1140-C344-A5, Release date 11.2012
Comments
Startup Time for warm motor
Temperature limit for cold motor
49 Thermal overload protection
49 K-Factor
Time Constant
49 Thermal Alarm Stage
Current Overload Alarm Setpoint
Kt-FACTOR when motor stops
Emergency time
49 Temperature rise at rated sec.
curr.
49 Temperature rise at rated sec.
curr.
66 Startup Counter for Motors
I Start / I Motor nominal
Maximum Permissible Starting
Time
Temperature Equalizaton Time
Rated Motor Current
Maximum Number of Warm
Starts
Number of Cold Starts - Warm
Starts
Extension of Time Constant at
Stop
Extension of Time Constant at
Running
Minimum Restart Inhibit Time
Rotor Overload Protection
Load Jam Protection
Load Jam Tripping Threshold
Load Jam Trip Delay
Load Jam Alarm Threshold
Load Jam Alarm Delay
Load Jam Blocking after motor
start
59 Overvoltage Protection
59-1 Pickup
59-1 Pickup
59-1 Time Delay
59-2 Pickup
59-2 Pickup
59-2 Time Delay
59-1 Pickup V2
59-2 Pickup V2
59-1 Dropout Ratio
59-2 Dropout Ratio
SIPROTEC, 7SK80, Manual

Advertisement

Table of Contents
loading