Siemens 7SK80 Manual page 354

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Technical Data
4.1 General Device Data
Profibus FO (DP)
DNP3.0 /MODBUS RS485
DNP3.0 /MODBUS FO
Ethernet electrical (EN 100) for
DIGSI
IEC61850
DNP3 TCP
PROFINET
or SICAM I/O unit 7XV5673
Ethernet optical (EN 100) for
DIGSI
IEC61850
DNP3 TCP
PROFINET
or SICAM I/O unit 7XV5673
354
FO connector type
Terminal
Transmission speed
Recommended:
Optical wavelength
Laser Class 1 according to EN
60825-1/-2
Permissible optical signal at-
tenuation
Bridgeable distance
Terminal
Test voltage
Transmission speed
Bridgeable distance
FO connector type
Terminal
Transmission speed
Optical wavelength
Laser Class 1 according to EN
60825-1/-2
Permissible optical signal at-
tenuation
Bridgeable distance
Terminal
Test voltage (with regard to the
socket)
Transmission speed
Bridgeable distance
Terminal
Transmission speed
Optical wavelength
Bridgeable distance
ST connector
Double ring
Back case bottom, mounting location "B"
Up to 1.5 MBd
> 500 kBd with normal casing
λ = 820 nm
When using glass fiber 50 μm 125 μm or
glass fiber 62.5 μm/125 µm
max. 8 dB, with glass fiber 62.5/125 µm
max. 2 km
Back case bottom, mounting location "B", 9-
pin DSUB socket
500 V; 50 Hz
Up to 19,200 Bd
max. 1 km
ST connector transmitter/receiver
Back case bottom, mounting location "B"
Up to 19,200 Bd
λ = 820 nm
When using glass fiber 50 μm/125 μm or
glass fiber 62.5 μm/125 µm
max. 8 dB, with glass fiber 62.5 μm/125 µm
max. 1.5 km
Back case bottom, mounting location "B",
2 x RJ45 socket
100BaseT in acc. with IEEE802.3
500 V; 50 Hz
100 Mbit/s
21.87 yd
Back case bottom, mounting location "B",
Duplex-LC, 100BaseF acc. to IEEE802.3
100 Mbit/s
1300 nm
max. 2 km (1.24 mi)
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012

Advertisement

Table of Contents
loading

Table of Contents