Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
Figure 2-7
Logic diagram of the 50N-2 element
If parameter 1313 MANUAL CLOSE is set to 50N-2 instant. or 50N-3 instant. and manual close de-
tection is used, a pickup causes instantaneous tripping even if the Element is blocked via a binary input.
62
SIPROTEC, 7SK80, Manual