Siemens 7SK80 Manual page 248

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Functions
2.17 Temperature Detection via RTD Box
For the RTD box, for example, the IP address 192.168.100.20 is entered as follows:
Figure 2-96
Device Settings
The settings are the same for each input and are here shown at the example of measuring input 1.
Set the type of temperature detector for RTD 1 (temperature sensor for measuring point 1) at address 9011
RTD 1 TYPE. You can choose between Pt 100 Ω , Ni 120 Ω and Ni 100 Ω. If no temperature detector
is available for RTD 1, set RTD 1 TYPE = Not connected. This setting is only possible via DIGSI at „Display
Additional Settings".
Address 9012 RTD 1 LOCATION informs the device on the mounting location of RTD 1. You can choose
between Oil, Ambient, Winding, Bearing and Other. The selection is not evaluated in the device but only
serves the purpose of providing information about the medium in which the temperature measurement is
carried out. This setting is only possible in DIGSI at „Display Additional Settings".
You can also set an alarm temperature and a tripping temperature. Depending on the temperature unit selected
in the Power System Data (Section 2.1.1.2 in address 276 TEMP. UNIT), the alarm temperature can be ex-
pressed in degrees Celsius (°C) (address 9013 RTD 1 STAGE 1) or degrees Fahrenheit (°F) (address 9014
RTD 1 STAGE 1). The tripping temperature is set to degrees Celsius (°C) in address 9015 RTD 1 STAGE 2
or to degrees Fahrenheit (°F) at address 9016 RTD 1 STAGE 2.
Note
There is no conversion when changing the temperature unit. You have to re-parameterize the threshold value
according to the selected unit.
The settings for all connected temperature detectors of the first and second RTD box. can be made accordingly.
248
DIGSI setting of the RTD box
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012