Siemens 7SK80 Manual page 235

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Addr.
Parameter
0
POWER
0
VOLTAGE SYSTEM
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
T TRIP DELAY
0A
T PICKUP DELAY
0
T PICKUP DELAY
0A
T DROPOUT DELAY
0A
BLK.by Vol.Loss
0A
DROPOUT RATIO
0A
DROPOUT RATIO
0
DO differential
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
C
Setting Options
Ia Va-n
Ib Vb-n
Ic Vc-n
Phase-Phase
Phase-Ground
0.05 .. 40.00 A
1A
0.05 .. 40.00 A
5A
0.25 .. 200.00 A
1A
0.001 .. 1.500 A
5A
0.005 .. 7.500 A
2.0 .. 260.0 V
2.0 .. 200.0 V
40.00 .. 60.00 Hz
50.00 .. 70.00 Hz
0.10 .. 20.00 Hz/s
1A
2.0 .. 10000.0 W
5A
10.0 .. 50000.0 W
-0.99 .. 0.99
15 .. 100 %
4 .. 100 V/s
2.0 .. 260.0 V
0.00 .. 3600.00 sec
0.00 .. 60.00 sec
0.00 .. 28800.00 sec
0.00 .. 60.00 sec
NO
YES
0.70 .. 0.99
1.01 .. 3.00
0.02 .. 1.00 Hz
2.15 Flexible Protection Functions
Default Setting
Ia Va-n
Power
Phase-Phase
Voltage System
2.00 A
Pickup Threshold
2.00 A
Pickup Threshold
10.00 A
0.100 A
Pickup Threshold
0.500 A
110.0 V
Pickup Threshold
110.0 V
Pickup Threshold
51.00 Hz
Pickup Threshold
61.00 Hz
Pickup Threshold
5.00 Hz/s
Pickup Threshold
200.0 W
Pickup Threshold
1000.0 W
0.50
Pickup Threshold
20 %
Pickup Threshold
60 V/s
Pickup Threshold
110.0 V
Pickup Threshold
1.00 sec
Trip Time Delay
0.00 sec
Pickup Time Delay
0.00 sec
Pickup Time Delay
0.00 sec
Dropout Time Delay
YES
Block in case of Meas.-
Voltage Loss
0.95
Dropout Ratio
1.05
Dropout Ratio
0.03 Hz
Dropout differential
Functions
Comments
235