Siemens 7SK80 Manual page 466

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Appendix
A.8 Settings
Addr.
Parameter
5422
FCT 81-2 O/U
5423
FCT 81-3 O/U
5424
FCT 81-4 O/U
7001
FCT 50BF
7004
Chk BRK CONTACT
7005
TRIP-Timer
7006
50BF PICKUP
7007
50BF PICKUP IE>
8101
MEASURE. SUPERV
8102
BALANCE V-LIMIT
8103
BAL. FACTOR V
8104
BALANCE I LIMIT
8105
BAL. FACTOR I
Σ I THRESHOLD
8106
Σ I FACTOR
8107
FAST Σ i MONIT
8109
8110A
T BAL. V LIMIT
8111A
T BAL. I LIMIT
8201
FCT 74TC
8202
Alarm Delay
8301
DMD Interval
8302
DMD Sync.Time
8311
MinMax cycRESET
8312
MiMa RESET TIME
8313
MiMa RESETCYCLE
8314
MinMaxRES.START
8315
MeterResolution
9000
UDP Port
9001
IP address[0]
9002
IP address[1]
466
Function
C
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
50BF BkrFailure
OFF
ON
50BF BkrFailure
OFF
ON
0.06 .. 60.00 sec; ∞
50BF BkrFailure
50BF BkrFailure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
50BF BkrFailure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Measurem.Superv
OFF
ON
Measurem.Superv
10 .. 100 V
Measurem.Superv
0.58 .. 0.90
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.90
0.05 .. 2.00 A; ∞
Measurem.Superv
1A
0.25 .. 10.00 A; ∞
5A
Measurem.Superv
0.00 .. 0.95
Measurem.Superv
OFF
ON
Measurem.Superv
0 .. 100 sec
Measurem.Superv
0 .. 100 sec
74TC TripCirc.
ON
OFF
74TC TripCirc.
1 .. 30 sec
Demand meter
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
Demand meter
On The Hour
15 After Hour
30 After Hour
45 After Hour
Min/Max meter
NO
YES
Min/Max meter
0 .. 1439 min
Min/Max meter
1 .. 365 Days
Min/Max meter
1 .. 365 Days
Energy
Standard
Factor 10
Factor 100
RTD-Box
0 .. 65535
RTD-Box
0 .. 255
RTD-Box
0 .. 255
Setting Options
Default Setting
OFF
OFF
OFF
OFF
OFF
0.25 sec
0.10 A
0.50 A
0.10 A
0.50 A
ON
50 V
0.75
0.50 A
2.50 A
0.50
0.10 A
0.50 A
0.10
ON
5 sec
5 sec
ON
2 sec
60 Min., 1 Sub
On The Hour
YES
0 min
7 Days
1 Days
Standard
5000
0
0
E50417-G1140-C344-A5, Release date 11.2012
Comments
81-2 Over/Under Frequency Pro-
tection
81-3 Over/Under Frequency Pro-
tection
81-4 Over/Under Frequency Pro-
tection
50BF Breaker Failure Protection
Check Breaker contacts
TRIP-Timer
50BF Pickup current threshold
50BF Pickup earth current
threshold
Measurement Supervision
Voltage Threshold for Balance
Monitoring
Balance Factor for Voltage
Monitor
Current Threshold for Balance
Monitoring
Balance Factor for Current
Monitor
Summated Current Monitoring
Threshold
Summated Current Monitoring
Factor
Fast Summated Current Monitor-
ing
T Balance Factor for Voltage
Monitor
T Current Balance Monitor
74TC TRIP Circuit Supervision
Delay Time for alarm
Demand Calculation Intervals
Demand Synchronization Time
Automatic Cyclic Reset Function
MinMax Reset Timer
MinMax Reset Cycle Period
MinMax Start Reset Cycle in
Meter resolution
UDP service port in the RTD box
IP address[0] of RTD box,
connec. by UDP
IP address[1] of RTD box,
connec. by UDP
SIPROTEC, 7SK80, Manual