Siemens 7SK80 Manual page 227

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Figure 2-84
Logic diagram of the flexible protection functions
The parameters can be set to monitor either exceeding or dropping below of the threshold. The configurable
pickup time delay will be started once the threshold (>-Element) has been exceeded. When the time delay has
elapsed and the threshold is still violated, the pickup of the phase (e.g. no. 235.2122 „$00 pickup A")and
of the function (no. 235.2121 „$00 picked up") is reported. If the pickup delay is set to zero, the pickup will
occur simultaneously with the detection of the threshold violation. If the function is enabled, the pickup will start
the trip time delay and the fault log. This is not the case if set to "Alarm only". If the threshold violation persists
after the trip time delay has elapsed, the trip will be initiated upon its expiration (no. 235.2126 „$00 TRIP").
The timeout is reported via (no. 235.2125 „$00 Time Out"). Expiry of the trip time delay can be blocked via
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
Functions
2.15 Flexible Protection Functions
227