Siemens 7SK80 Manual page 458

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Appendix
A.8 Settings
Addr.
Parameter
676
S2W month
677
S2W week
678
S2W day
679
S2W hour
700
GOOSE-Stop
1101
FullScaleVolt.
1102
FullScaleCurr.
1107
I MOTOR START
1108
P,Q sign
1201
FCT 50/51
1202
50-2 PICKUP
1203
50-2 DELAY
1204
50-1 PICKUP
1205
50-1 DELAY
1207
51 PICKUP
1208
51 TIME DIAL
1209
51 TIME DIAL
1210
51 Drop-out
1211
51 IEC CURVE
1212
51 ANSI CURVE
1213A
MANUAL CLOSE
1214A
50-2 active
1215A
50 T DROP-OUT
1216A
50-3 active
1217
50-3 PICKUP
1218
50-3 DELAY
1219A
50-3 measurem.
1220A
50-2 measurem.
1221A
50-1 measurem.
458
Function
C
Device, General
1 .. 12
Device, General
1 .. 5
Device, General
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Device, General
1 .. 24
Device, General
YES
NO
P.System Data 2
0.10 .. 800.00 kV
P.System Data 2
10 .. 50000 A
P.System Data 2
1A
0.40 .. 10.00 A
5A
2.00 .. 50.00 A
P.System Data 2
not reversed
reversed
50/51 Overcur.
ON
OFF
0.10 .. 35.00 A; ∞
50/51 Overcur.
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
0.10 .. 35.00 A; ∞
50/51 Overcur.
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
50/51 Overcur.
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
0.05 .. 3.20 sec; ∞
50/51 Overcur.
0.50 .. 15.00 ; ∞
50/51 Overcur.
50/51 Overcur.
Instantaneous
Disk Emulation
50/51 Overcur.
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
50/51 Overcur.
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50/51 Overcur.
50-3 instant.
50-2 instant.
50 -1 instant.
51 instant.
Inactive
50/51 Overcur.
Always
50/51 Overcur.
0.00 .. 60.00 sec
50/51 Overcur.
Always
1.00 .. 35.00 A; ∞
50/51 Overcur.
1A
5.00 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
50/51 Overcur.
Fundamental
True RMS
Instantaneous
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
Setting Options
Default Setting
10
5
Sunday
3
NO
20.00 kV
400 A
2.50 A
12.50 A
not reversed
ON
4.00 A
20.00 A
0.00 sec
1.00 A
5.00 A
0.50 sec
1.00 A
5.00 A
0.50 sec
5.00
Disk Emulation
Normal Inverse
Very Inverse
50-2 instant.
Always
0.00 sec
Always
∞ A
∞ A
0.00 sec
Fundamental
Fundamental
Fundamental
E50417-G1140-C344-A5, Release date 11.2012
Comments
month of time set summer to
winter
week of time set summer to
winter
day of time set summer to winter
hour of time set summer to winter
GOOSE-Stop
Measurem:FullScaleVolt-
age(Equipm.rating)
Measurem:FullScaleCur-
rent(Equipm.rating)
Motor Start Current (Block 49,
Start 48)
P,Q operational measured values
sign
50, 51 Phase Time Overcurrent
50-2 Pickup
50-2 Time Delay
50-1 Pickup
50-1 Time Delay
51 Pickup
51 Time Dial
51 Time Dial
Drop-out characteristic
IEC Curve
ANSI Curve
Manual Close Mode
50-2 active
50 Drop-Out Time Delay
50-3 active
50-3 Pickup
50-3 Time Delay
50-3 measurement of
50-2 measurement of
50-1 measurement of
SIPROTEC, 7SK80, Manual

Advertisement

Table of Contents
loading

Table of Contents