Siemens 7SK80 Manual page 295

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Switching Mode
The switching mode serves for activating or deactivating the configured interlocking conditions at the time of
the switching operation.
The following switching modes (local) are defined:
• For local commands (CS = LOCAL)
– locked (normal) or
– unlocked (unlatched) switching.
With a 7SK80, the switching mode can be changed between "locked" and "unlocked" on the operator panel
after having entered the password or by means of CFC also via binary inputs and a function key.
The following switching modes (remote) are defined:
• For remote or DIGSI commands (CS = LOCAL, REMOTE or DIGSI)
– locked or
– unlocked (unlatched) switching. Here, deactivation of the interlocking is accomplished via a separate un-
locking command.
– For commands from CFC (CS = Auto), please observe the notes in the CFC manual (component: BOOL
to command).
Zone Controlled / Field Interlocking
Zone controlled / field interlocking (e.g. via CFC) includes the verification that predetermined switchgear posi-
tion conditions are satisfied to prevent switching errors (e.g. disconnector vs. ground switch, ground switch only
if no voltage applied) as well as verification of the state of other mechanical interlocking in the switchgear bay
(e.g. High Voltage compartment doors).
Interlocking conditions can be programmed separately, for each switching device, for device control CLOSE
and/or OPEN.
The enable information with the data "switching device is interlocked (OFF/NV/FLT) or enabled (ON)" can be
set up,
• directly, using a single-point or double-point indication or internal message (tagging), or
• by means of a control logic via CFC.
When a switching command is initiated, the actual status is scanned cyclically. The assignment is done via "Re-
lease object CLOSE/OPEN".
System Interlocking
Substation Controller (System interlocking) involves switchgear conditions of other bays evaluated by a central
control system.
Double Activation Blockage
Parallel switching operations are interlocked. As soon as the command has arrived all command objects
subject to the interlocking are checked to know whether a command is being processed. While the command
is being executed, interlocking is enabled for other commands.
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
Functions
2.21 Command Processing
295