Fire; Entry; Push Set; Pa Silent - ADEMCO Galaxy 16 Engineer's Manual

8–16 zone security control panel
Table of Contents

Advertisement

This zone type records the active (+) and restore (–) events in the log.
Note: Keyswitch zones programmed as codes 1, 2 and 3 are recorded in the
Event Log (and transmitted via SIA communications) as users 18, 19 and
20 respectively. If the user codes options 1, 2 or 3, (Usr1 – Usr3) are
assigned codes any entry of these codes will be recorded as Users 1 to 3.
For details on user code attributes refer to
– Codes; Programming Codes and Code Attributes

05 Fire

This zone type is continuously operational.
When activated, a Fire zone overrides the Bell Delay parameter. The keypad
buzzer and control panel horn output, if fitted, emit an interrupted tone (one sec-
ond on, 0.5 seconds off), easily distinguishable from all other alarm conditions.
Any valid code entry cancels the fire activation.
This zone type records the active (+) events in the log.

06 Entry

The function of this zone type is to initiate the unsetting procedure on entering a
set system. Activation of the zone starts the Entry Time. This zone type is used in
conjunction with Push-to-Set systems.

07 Push Set

A Push-to-Set (Exit Terminator) zone is used to terminate the setting procedure of
a system. When the system is set the zone has no other function. The Push-to-Set
zone does not start the unsetting of a system.
08 PA
The PA (Personal Attack) function is continuously operational. Activation of this
zone type overrides the Bell Delay parameter and causes an instant full alarm
condition that requires to be reset with a code authorised for PA reset, see
5: MENU OPTIONS: Option 4 – Codes
This zone type records the active (+) events in the log.
Note: If a PA zone is open, it is indicated on the keypad whenever a valid code
is entered. The part that the open PA is assigned to cannot be set.
PA Delay: If the PA Delay parameter is enabled, there is a 30 second delay be-
tween the activation of a PA zone and the alarm outputs firing. Resetting the PA
button during the delay period aborts the alarm. See
Option 6 – Parameters; 06 User Options; 05 PA Delay

09 PA Silent

The PA Silent zone operates in the same way as the PA zone except that there is no
audible or visual indication of the activation; that is, no bells or strobes are
activated. Only the remote communicator signals the alarm. This zone type records
the active (+) events in the log.