To programme the SIA triggers:
• Go to the triggers option and press the ent key.
• Trigger 1 Fire is displayed. If the box on the top line of the keypad display
is empty the trigger is disabled, if the box is filled the trigger is enabled.
• The # key toggles the enable status of the trigger.
• The A and B keys can be used to view the other triggers.
• Press ent to accept the programming or esc to cancel.
Figure 6.3 SIA Triggers Programming gives an example of programming the SIA
triggers, it shows how to enable trigger 4 Set/Reset.
07=TRIGGERS
ENT,01—15=SELECT
(a)
Triggers banner.
4 SET/RESET
#,4=ENABLE
(c)
Trigger four is currently
disabled.
Use the A or B key to scroll through the triggers, use the # key, or the
corrosponding No. key, to toggle the enable status of the displayed trigger.
z
8
PART SET/UNSET
ENABLE
(e)
Trigger 8 Part Set/Unset
enabled.

08 Autotest

An Engineer Test can be automatically transmitted to the Monitoring Station at
programmed intervals. The engineer uses this option to enter the time that the
first Engineer Test is transmitted. Subsequent Engineer Test transmissions are
offset by the value in
12 = Communications 1 (cont'd)
Press ent to select
the triggers option.
Use the A key to scroll through the triggers to trigger 4 Set/Reset.
press # or 4 to toggle
the enable status of
the trigger.
Press ent to accept the
triggers programming (esc
cancels).
Figure 6.3 SIA Triggers Programming.
.
09 Interval
1 FIRE
#,1=ENABLE
(b)
Trigger 1 Fire is displayed with its
enable status (empty box= disabled).
z
4
SET/RESET
ENABLE
(d)
Trigger 4 Set/Reset is now
enabled.
07=TRIGGERS
ENT,01—15=SELECT
89