Model FX2N-10PG Pulse Output Block
7.2.18

BFM#27 Operation pattern

The operation pattern executed by FX
TO commands from the PLC select an operation pattern in which it is operated by turning ON/
OFF each bit.
Bit No.
1st-speed
b0
positioning
operation
Interrupt 1st-
b1
speed positioning
operation
2nd-speed
b2
positioning
operation
Interrupt 2nd-
b3
speed positioning
operation
Interrupt stop
b4
operation
b5
Table operation
Variable speed
b6
operation
Manual pulse
b7
generator input
operation
b8 to b15 Not defined.
Operation
pattern
When b0 is ON, the 1st-speed positioning operation is selected.
Turn ON b0, and write relevant data into the target address Ι (BFM#14,
#13) and operation speed Ι (BFM#16, #15). Then turn ON START input
or START flag (BFM#26 b9), and the positioning operation will begin.
When b1 is ON, the interrupt 1st-speed positioning operation is
selected.
Turn ON b1, and write relevant data into the target address Ι (BFM#14,
#13) and operation speed Ι (BFM#16, #15). Then turn ON START input
or START flag (BFM#26 b9), and the positioning operation will begin.
Use X0 for the interrupt input.
When b2 is ON, the 2nd-speed positioning operation is selected.
Turn ON b2, and write relevant data into the target address Ι (BFM#14,
#13), target address ΙΙ (BFM#18, #17), operation speed Ι (BFM#16,
#15) and operation speed ΙΙ (BFM#20, #19). Then turn ON START input
or START flag (BFM#26 b9), and the positioning operation will begin.
When b3 is ON, the interrupt 2nd-speed positioning operation is
selected.
Turn ON b3, and write relevant data into the target address Ι (BFM#14,
#13), target address ΙΙ (BFM#18, #17), operation speed Ι (BFM#16,
#15) and operation speed ΙΙ (BFM#20, #19). Then turn ON START input
or START flag (BFM#26 b9), and the positioning operation will begin.
Use X0 and X1 for the interrupt input.
When b4 is ON, the interrupt stop operation is selected.
Turn ON b4, and write relevant data into the target address Ι (BFM#14,
#13) and operation speed Ι (BFM#16, #15). Then turn ON START input
or START flag (BFM#26 b9), and the positioning operation will begin.
Use X0 for the interrupt input.
Positioning operation in the table system is executed. START command
(START input or BFM#26 b9) executes the operation form the table No.
instructed with BFM#98. (BFM#100 to BFM#1299 are used.)
When b6 is ON, the variable speed operation is selected.
Turn ON b6 and write the speed data into the operation speed Ι
(BFM#16, #15), and the variable speed operation will start immediately.
It is not necessary to turn ON the START input or START flag (BFM#26
b9).
When b7 is ON, the manual pulse generator input operation is selected.
Turn ON b7, and apply the manual pulse generator input, and the pulses
will be output to the motor.
Input from the manual pulse generator is done with φA and φB.
It is not necessary to turn ON the START input or START flag (BFM#26
b9).
-10PG is assigned to each bit.
2N
Remarks
Buffer memory (BFM) 7
7-11