Model FX2N-10PG Pulse Output Block
8.4.5

Positioning complete flag

The positioning complete flag (BFM#28 b6) is reset with START input, START command
(BFM#26 b9), forward jog (BFM#26 b4), reverse jog (BFM#26 b5), zero return (BFM#26 b6),
data set type zero return (BFM#26 b7), variable-speed operation, manual pulse generator
input operation or power shutdown, and is turned ON when the target address is reached.
However, it is not reset with START input or START command when the travel is 0.
(If it is OFF before start of positioning, it is turned ON.)
• When positioning operation is stopped with STOP command, the positioning complete flag
(BFM#28 b6) is not turned ON.
If the STOP command is received in the deceleration process to the target address, it is
stopped when it arrives at the target address, as the gradient of deceleration will be the
same.
At this time, the positioning complete flag (BFM#28 b6) is not turned ON.
8.4.6

STOP command

When STOP command (BFM#26 b1) is turned ON, the work is decelerated and stopped.
When it is restarted, the operation is different depending on the setting of the parameter
(BFM#36 b15).
BFM#36 b15=0 : The remaining-distance operation is executed with restart.
BFM#36 b15=1 : The 1st-speed positioning operation is ended, and the next new
positioning operation is started.
Operation pattern 8
8-13