Machine Signature

Overview
The acceptance test for systems with safety integrated functions focuses on validating the
functionality of safety integrated monitoring and stop functions configured in the Wireless Remote
Control System.
The purpose of the test is to verify proper configuration of the defined safety functions and test
mechanisms and to examine the response of dedicated monitoring functions to explicit input of
values outside the tolerance limits.
The test must cover all Wireless Remote Control System-specific safety configured monitoring
functions and global safety integrated functionality in eXLhoist.
Condition Prior to Acceptance Test
The machine is wired up correctly.
All safety devices such as limit switches, overload sensors, and emergency stop switches are
connected and ready for operation.
All commissioning parameters must be correctly set on the Wireless Remote Control System.
Acceptance Test Process
Step
Action
1
Select the Base Station and the Remote Device
2
Configure the relay assignments by functions.
3
Configure the interlocking assignments (optional)
4
Define passwords (optional):
E-STOP
STOP
Configuration
Configure:
Timeout
UOC delay
Motion enable / limit switch
5
Select the Microsoft® Excel acceptance test
template file in www.schneider-electric.com.
Complete the acceptance test template according to
the system specificities.
Mark down the configuration signature thanks to the
eXLhoist Configuration Software.
EIO0000001505 12/2014
Comment
With the eXLhoist Configuration Software
With Microsoft® Excel
The acceptance test template is a generic
acceptance test for generic application. The
acceptance report must be updated according
to the system application.
The signature allows you to compare the
checksum value with the one displayed in the
identification menu on the graphic display.
Safety
75