E-Stop - Harmony eXLhoist User Manual

Wireless remote control system
Table of Contents

Advertisement

Safety

E-STOP

Overview
For general descriptions, refer to E-STOP function
The E-STOP is not configurable.
The undesired event of the E-STOP function is masking of E-STOP activation.
The safe state of the E-STOP function is to open safety relays.
Function
Installation

E-STOP

With auxiliary
contact loop
between S2_S3
and IN0
Without auxiliary
contact loop
between S2_S3
and IN0
For a SIL3 PLe E-STOP, auxiliary contact of contactors must be mechanically linked. Contactors
shall be compliant with:
EN 60947-4-1:2010 Annex F (preferred) - Requirements for auxiliary contact linked to power
contact (mirror contact), or
EN 60947-5-1:2004 Annex L - Special prescription for elements with contact mechanically
linked.
In order to be compliant with the Common Cause of Failure (CCF), wiring of redundant contactors
or drives must be by different path.
The standard E-STOP function of eXLhoist is limited to a stop category 0 according to IEC 60204-
32. If some applications require an E-STOP function with a stop category 1, then a safety relay type
Preventa XPS ATE or XPS AV or similar must be used.
In order to justify of the safety category 4 according to ISO13849-1, an automatic diagnostic is
realized on IN0 terminal thanks to the S2_S3 terminal (Pulsed 12 V). An external supply of IN0
input cannot be used.
E-STOP function is a passive stop (function activated when an invalid frame is detected).
64
(see page
IEC 60204-32
IEC 61508
STOP
SIL
category
Category
SIL3
SIL2
121).
IEC 62061
ISO 13849
SIL CL
Safety
category
SIL3 CL
Safety
category
SIL2 CL
Safety
category
EIO0000001505 12/2014
PL
PL e