Safeguarding Function

Overview
The ZARB18• Base Station implement 12 inputs IN7...IN18.
These inputs are dedicated for limit switches to provide a protection to the hoist system.
Description
There are 4 limit switches per axis that allow to:
Stop the motion at minimum mechanical position.
Disable the high speed of the direction when the hoist system is near the minimum position.
Stop the motion at maximum mechanical position.
Disable the high speed of the direction when the hoist system is near the maximum position.
These inputs are associated to motion buttons.
Once a limit switch is opened, the associated motion relay(s) is(are) switched OFF.
You can configure the limit switches with the eXLhoist Configuration Software
Installation Principle
Principle of safeguarding function installation for 1 axis:
1
Mechanical target for limit switch triggering for stopping the motion direction
2
Mechanical target for limit switch triggering for slowing the motion direction
3
Mechanical target for limit switch triggering for slowing the motion direction
4
Mechanical target for limit switch triggering for stopping the motion direction
5
Stationary part
6
Mobil part
7
Motion (example: button 1 or 1H)
8
Motion (example: button 2 or 2H)
General Wiring Rules
The I/O and power supply cables should be AWG 16 (cross-sectional conductor area = 1.3 mm
The I/O and power supply cable lengths should not exceed 20 m (65.6 ft).
For more details, refer to Wiring Best Practices
EIO0000001505 12/2014
(see page
91).