After changeover, the screen below appears.
15/07/09
19:10 :00
GS 1
Rental application
Stop
Faults
Alarms
A651: Temporary power grid single Genset
coupling
Validation
Grid CT ratio
20.0
5. To enter the value of the grid current transformer ratio: press the "GRID CT RATIO" button on the touch screen.
 Using the alphanumeric keys of the MICS KERYS: enter the value of the CT ratio in tenths.
Example: CT = 100A/5A (calculation: 100/5 = 20 ; 20 x10= 200 ) value to be entered 200 .
CT BUSBAR/Grid setting 1 (1/10)
0<=
0200
<=32767
Valid
Esc.
6. Then press " VALID " .