Power Supply Sensor (Code 9.3, SID 232/SPN 620)
Cause
Shortcut
Fault in sensor
Memory Fault EMS (Code 9.9, SID 240/SPN 628)
Cause
Memory fault in engine man-
agement system
Faulty data link (J1587) (Code 9.2, SID 250/SPN 608)
Cause
Faulty data link
Data Set Memory EEPROM, CIU (Code 9.8, SID 253/SPN 630)
Cause
Internal fault in control mod-
ule
Programming faulty
Data Set Memory EEPROM, EMS (Code 9.9, SID 253/SPN 630)
Cause
Internal fault in control mod-
ule
Internal fault in control mod-
ule
Fault in Control Unit, CIU (Code 9.8, SID 254/SPN 629)
Cause
Faulty EEPROM, CIU
Faulty flash memory, CIU
Fault in control module, CIU
Control Module EMS (Code 9.9, SID 254/SPN 629)
Cause
Internal fault in control mod-
ule
7748681 12-2011
Reaction
Faulty values in oil pressure
and boost pressure sensors
Fault code for oil pressure-
and boost pressure sensor
Low engine output
The instrument shows zero oil
pressure and boost pressure
Reaction
Engine might not start
Reaction
None
Reaction
Engine does not start
Reaction
Engine does not start
Reaction
CIU returns to factory setting
Engine goes to idle
Engine can not be started
Reaction
Engine misfires
Engine does not start
175/298
Fault Code Register
Remedy
Check that the cable harness
to oil pressure and boost
pressure sensor has not been
damaged
Check oil pressure and boost
pressure sensors
Remedy
Re-program the unit
Remedy
Check that the 8-pin connec-
tor is not damaged
Check that the cables
between the CIU/DCU and
the engine management unit
are not damaged
Remedy
Re-program the control mod-
ule.
Remedy
Re-program the control mod-
ule. If the fault remains,
change the control module
Remedy
Re- program the unit
Remedy
Change engine control unit