Activation Of An Alarm And A Fault - SDMO RENTAL POWER R550C2 User And Maintenance Manual

Generating sets
Table of Contents

Advertisement

6.2.4.3.

Activation of an alarm and a fault

The appearance of an alarm and a fault causes:
The yellow and red LEDs to flash
the related screen to be displayed (example below)
FAULTS 1/2
FAULT
Emergency Stop
25/12/05 15:30
Esc=RESET
The faults list can be accessed by pressing OK (of the scrolling and selection wheel) (examples below)
FAULTS
1/2
FAULT 25/12/05 15:30
Emergency Stop
ALARM 25/12/05 15:30
Low Fuel Level

OK=HELP
HELP
Check:
- Emerg. Stop Pos.
- Connector(s)
Esc
If the alarm is no longer active, it is reset automatically (cause disappears).
Press Esc to reset a fault:
reset acknowledged if the cause of the fault has been removed
-
-
reset not performed if the cause of the fault is still present.
If several faults are present, the number of faults is
displayed at the top of the screen.
OK=LIST
Press Esc to return to the previous screen.
Press OK to go to the HELP screen (help on the
highlighted fault)
Use the scrolling and selection wheel to scroll through
the list of faults.
Esc
50/298

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents