Back-up to perform
A612: Single Genset without N/E
Mains supply detection using the adjustment card
Mains supply detection using an external contact
7. The KERYS saves your new configuration.
8. After return to the KERYS home screen,
The configuration will only be taken into account if the following operations are carried out:
Important
Solo generating set, CRF coupling (A651)
1. Turn off the battery isolator switch.
2. Check that the emergency stop buttons are activated.
3. Press the "STOP" button of the KERYS.
4. Turn the changeover switch to position 4.
1: SOLO GENERATING SET WITHOUT GRID COUPLING
APPLICATION: A612
2: PRODUCTION POWER PLANT WITHOUT GRID COUPLING
APPLICATION: A632 / A633
3: NOT APPLICABLE
4 : SOLO GENERATING SET WITH GRID COUPLING
APPLICATION: A651
GS 1
Saving in flash ...
Turn on the battery isolator switch.
Wait 5 seconds.
Turn off the battery isolator switch.
(If the switch is already set to " 4 ", turn the switch and return to position '' 4 '')
Rental application
Validation
95/298
Stop
Faults
Alarms
1
2
4