5. Select the configuration of the mains detection of the generating set by clicking directly on the touch screen.
 For a mains detection by means of the regulation card you must select the configuration "Mains supply detection using
the adjustment card" and connect the voltage reference to the terminals Xcbc1 - 1-2-3 .
 For mains detection by an external switch you must select the configuration "Mains supply detection using an external
contact" and connect the external switch to the terminals Xcbc3 - 34-35 .
 For starting by means of an external switch you must select the configuration "Mains supply detection using an external
contact" and connect the external switch to the terminals Xcbc3 - 32-33 .
 For solo starting , in the absence of a mains connection, you must select the configuration "Mains supply detection using an
external contact" . No connection is necessary.
N.B. selecting detection depends on the connection made according to Section "Connections of the
generating sets".
Important
15/07/09
19:10 :00
A612: Single Genset without N/E
Mains supply detection using the adjustment card
Mains supply detection using an external contact
6. Press "Validation" on the touch screen.
GS 1
Rental application
Validation
94/298
Stop
Faults
Alarms