Configuration in solo generating set

Without Normal/Emergency inverter (A612)
This configuration is designed to provide:
The generation of electricity for an installation from an external starting command (dry contact).
The generation of electricity for an installation in forced operation.
Automatic operation (Kerys in "AUTO" mode)
Loss of grid voltage
Generating set start request (dry contact, switch, clock, etc.).
The speed and voltage of the generating set increase.
Generating set power unit switched off after voltage and frequency stabilisation.
Return of grid voltage
Dry contact, switch, clock, etc. switched on.
Cooling delay.
Generating set stopped and set to standby.
FORCED OPERATION (Kerys in "AUTO" mode)
Start of FORCED OPERATION
Generating set start request (dry contact, switch, clock, etc.).
The speed and voltage of the generating set increase.
Generating set power unit switched off after voltage and frequency stabilisation.
End of FORCED OPERATION
Dry contact, switch, clock, etc. switched on.
Generating set power unit switched on.
Cooling delay.
Generating set stopped and set to standby.
Manual operation of generating set
This mode of operation is selected with the "MANU" key (on the front of the MMI module). The operator is able to start and stop the
generating set by using the MMI keypad. The generating set power unit is switched off by means of the MMI keys. The safety devices
of the generating set remain active in this mode of operation.
M
Application (load)
The installation is supplied by the generating set
The Kerys remains in "AUTO" mode
This mode of operation is the responsibility of the operator.
3PH
Regulation
module
3PH + N
Base
module
MMI module