JUMO LOGOSCREEN Operating Manual page 74

Paperless recorder with compactflash card as storage medium
Hide thumbs Also See for LOGOSCREEN:
Table of Contents

Advertisement

4 Configuration parameters
Control signal
(display off)
Calibration status
(fine calibration)
Actual start value
(fine calibration)
Target start value
(fine calibration)
Actual end value
(fine calibration)
Target end value
(fine calibration)
Example for
fine calibration
Date
Time
74
Parameterization
Display off
Control signal
Parameterization
Fine calibration
Analog input 1—12
Calibration
status
Parameterization
Fine calibration
Analog input 1—12
Actual start val.
Parameterization
Fine calibration
Analog input 1—12
Target start val.
Parameterization
Fine calibration
Analog input 1—12
Actual end val.
Parameterization
Fine calibration
Analog input 1—12
Target end val.
Systematic errors, such as those caused by an unsuitable probe mounting, for
example, can be compensated through fine calibration.
Example: A probe provides measurements that cover a temperature range from
200 to 300 °C. It has been installed in a tunnel oven so unfavorably as to always
indicate 10°C less than the temperature of the charge. The incorrect measurement
can be corrected through fine calibration.
Actual start value : 200°C
Target start value : 210°C
Actual end value
: 300°C
Target end value
: 310°C
Parameterization
Date and time
Date
Parameterization
Date and time
Time
Off,
LogInp.1 — 7,
Alarm Gr.1 — 6,
Combination alarm,
Logged in,
Error, Modbus flag,
Ext. Inp. 1 — 6,
CF plugged in, stolen CF,
Int. mem. al./CF,
int. mem. al./ser,
Mem. al./CF card
Off,
On
-99999 to 0 to +99999
-99999 to 0 to +99999
-99999 to 1000 to +99999
-99999 to 1000 to +99999
any date
any time
If the selected input or
signal is activated, the
display is switched off. The
parameter can only be
entered if the parameter
Switch-off event is set to
"Control signal".
A calibration (adjustment)
of the analog
measurements can be
activated here. The
adjustment is carried out
using a linear equation.
Start value of the
actual line.
Only active when
calibration status = On.
Start value of the
target line.
Only active when
calibration status = On.
End value of the
actual line.
Only active when
calibration status = On.
End value of the
target line.
Only active when
calibration status = On.
Entry of the current date
Entry of the current
time