Operating Modes - JUMO LOGOSCREEN Operating Manual

Paperless recorder with compactflash card as storage medium
Hide thumbs Also See for LOGOSCREEN:
Table of Contents

Advertisement

2 Instrument description

2.7 Operating modes

3 operating
modes
Stored value
Storage cycle
Normal
operation
Timed
operation
Event operation
Priority
Active
operating mode
24
The instrument has three operating modes:
- normal operation
- timed operation
- event operation
The following settings can, among others, be made for each of the three
operating modes:
- stored value
- storage cycle
The stored value determines whether the average/minimum/maximum value of
the time interval between two storage cycles or the instantaneous value is
stored.
The storage cycle determines the interval between two stored values. The
diagram speed corresponds to the storage cycle, which means that with a
storage cycle of 5sec, for example, the stored value is entered in the diagram
every 5sec.
Normal operation is active whenever event or timed operation is not active.
For timed operation, a period of time can be defined (up to 24 hrs) within
which a specific stored value and a specific storage cycle are active.
Event operation is active as long as its control signal (v page 84) is active.
Event operation can be used, for example, to shorten the storage cycle when a
combination alarm is present.
The respective priorities of the operating modes are allocated as follows:
Operating mode
Priority
Normal operation
3 (lowest)
Timed operation
2
Event operation
1 (highest)
The active operating mode is shown in the horizontal and vertical diagrams by
the background color of the display for the diagram speed:
Operating mode
Normal operation
Timed operation
Event operation
v Chapter 3.2.1 "Vertical diagram"
Chapter 3.2.2 "Horizontal diagram"
Color
gray
blue
orange