2.6 Integrator

Activating the
integrator
Example
In addition to minimum, maximum and average value of an (analog) channel in
a group, the reports can include an integrator.
An integrator time base has to be specified at the configuration level under
Configuration
Analog inputs
parameters, or Configuration
Additional parameters. If no time base is given (Off), the indication of the
integrator in the reports is suppressed.
The integrator can be used to determine a total flow volume or a liquid level,
for instance, and to present it in the diagram.
A sensor at analog input 1 provides a signal that is proportional to the flow rate
3
(m
/h). The volume (m
the integrator.
The following settings are required:
Parameter
Configuration
Analog inputs
Analog input 1
Additional
parameters
Unit
Configuration
Analog inputs
Analog input 1
Additional
parameters
Integr.
time base
Configuration
Analog inputs
Analog input 1
Additional
parameters
Integr. unit
2 Instrument description
Analog input 1 — 12
Analog inputs
3
) which has passed through is to be measured using
Value/selection
3
m
/h
Hour
3
m
Additional
External input 1 — 36
Description
Sensor signal proportional
3
to the flow rate in m
/h
The flow is measured in
3
m
/hour (h).
In the reports, the volume
which has passed through
3
is indicated in m
. The
maximum integrator value
is 99999.
23