WaterLogic WL100 Operating, Installation And Service Manual page 55

Hide thumbs Also See for WL100:
Table of Contents

Advertisement

 
Irregular / Intermittent Dispensing from one side  
 
 
Possible Reason 
Too much water pressure.  
Recommend 40 to 60 psi for 
the WL100 Water Treatment 
System to operate properly. 
Loose or bad connection on 
the Front Dispensing PCGB or 
Solenoid Connector 
Solenoid  
Dispensing button is broken on 
PCB 
 
 
Dispensing Won't Stop When Not Holding the Dispensing Button 
 
 
Possible Reason 
Stem of the switch is broken 
on the PCB ‐ Printed Circuit 
Board.  
Debris in the Solenoid  
Dispensing Button Stuck 
 
 
WL100 Operating, Installation, and Service Manual                     Page 55                                                 Revision: 5‐20‐2016 
DISPENSING TROUBLESHOOTING 
Check water pressure at the inlet bulkhead with a water pressure 
gauge. 
 
Additional method of verification is to turn off water to unit and 
press the dispense button.  Does the solenoid open without water 
pressure to the unit?  Listen for solenoid to activate, not button 
"click". 
 
Adjust water pressure to 40‐60 psi. 
Check that they are connected properly and tightened. 
If both the Water Pressure and PCB have been ruled out, then it is 
the Solenoid. 
 
Replace Solenoid. 
Check PCB for loose or damaged button.  Replace PCB as 
necessary. 
Remove Dispensing PC and inspect switches.   
 
Replace Dispensing ay PCB if switches appear broken. (Part 
Number EN‐6130 – WLCP PN 20‐0040)  
Inspect Solenoid for debris and clean out as needed. 
Dirt or Foreign material is filling the gap around the push‐buttons. 
Inspect the push buttons and clean surrounding area.  Inspect 
faucet assembly inside the unit and clean as necessary. 
 
Solution 
Solution 

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents