Compressor is Not Running 
 
 
Possible Reason 
Red Heater and Compressor 
Switch button on unit is in the 
off position 
Compressor Starting Circuit 
 
 
 
WL100 Operating, Installation, and Service Manual                     Page 53                                                 Revision: 5‐20‐2016 
 
 
Turn Red Heater and Compressor Switch on.   
I = ON 
 
 
Turn Red Heater and Compressor Switch off.  O = 
OFF. 
 
Remove the compressor cap on side of the 
compressor;   
 
Disconnect the black and red terminal connectors;  
 
Inspect the starter and overload relay for any defects.   
 
Replace components(s) as needed. 
 
Turn Red Heater and Compressor Switch on I = ON and retest 
compressor operation. 
 
Solution 