Troubleshooting
2.37 Humidifying Fan Outlet Thermistor Abnormality / Heater
Temperature Abnormality
PH
Remote
Controller Display
Method of
Detect short circuit and wire breakage of humidification thermistor.
When humidifying fan outlet temperature becomes high, this condition is identified as an
Malfunction
abnormal heater temperature fault.
Detection
Malfunction
When power is supplied and the thermistor input is 4.92 V or more, or 0.06 V or less.
If the humidifying fan outlet temperature is more than 90°C, this condition is identified as
Decision
abnormal heater temperature fault.
Conditions
Supposed
Causes
165
Short circuit and wire breakage of humidifying thermistor
Disconnected connector
Heater has a high power
Thermistor temperature detection error
Defective rotor motor
Defective hygroscopic fan motor
Defective heater control part
Defective humidifying fan
SiBE12-908
Service Diagnosis