SiBE12-908
1.2

Jumper Settings

1.2.1 When 2 Units are Installed in 1 Room
When 2 indoor units are installed in 1 room, one of the 2 wireless remote controllers can be set
for different address.
How to set the different address
(1) Remove the shield plate of the electrical box.
(2) Cut the address jumper JA on the control PCB.
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
1.2.2 Jumper Setting
(On indoor unit PCB)
Others
Control PCB of the indoor unit
(Refer to the removal procedure on page 194)
Wireless remote controller
J4
J4
ADDRESS
EXIST
1
CUT
2
Jumper
Function
JC
Power failure
recovery function
JB
Fan speed setting
when compressor is
OFF on thermostat.
(effective only at
cooling operation)
ADDRESS
JA
JA
ADDRESS
EXIST
1
CUT
2
(R8250)
When connected
(factory set)
Auto-restart
Fan speed setting ;
Remote controller
setting
Others
(R8249)
When cut
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
Fan rpm is set to "0"
<Fan stop>