SiBE12-908
5. Refilling the refrigerant.
Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like "liquid filling siphon
attached" displayed on it.)
Filling a cylinder with an attached siphon
2) Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.
6. Charging with refrigerant.
• If the total length of piping for all rooms exceeds 20m, additionally charge with (R410A) 20g of refrigerant for each additional
meter of piping.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Do not vent gases into the atmosphere.
Refrigerant type:R410A
(1)
GWP
value:
(1)
GWP = global warming potential
Please fill in with indelible ink,
the factory refrigerant charge of the product,
the additional refrigerant amount charged in the field and
+
the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).
Contains fluorinated greenhouse gases covered by
the Kyoto Protocol
6
5
NOTE:
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the
appropriate official national language on the unit. Therefor an additional multilingual fluorinated greenhouse
gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of that label.
CAUTION
1) Even though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a long
period of time.
2) Do not overfill with refrigerant. This will break the compressor.
Installation / Operation Manual
Stand the cylinder upright when filling.
There is a siphon pipe inside, so the
cylinder need not be upside-down to fill
with liquid.
1975
4
1
2
3
Filling other cylinders
Turn the cylinder upside-down
when filling.
1 factory refrigerant charge of the product: see unit name plate
2 additional refrigerant amount charged in the field
3 total refrigerant charge
4 Contains fluorinated greenhouse gases covered by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and manifold for charging
Installation Manual