Indoor Unit
1.8

Removal of Heat Exchanger

Procedure
Step
1. Disconnecting the
refrigerant pipe
Remove the screws
1
which fix the heat
exchanger to the
installation plate.
2
Release the 2 hooks at
the bottom.
Lift the indoor unit by a
wooden base.
3
Lift up the indoor unit
body slightly and pull
out the drain hose. (In
the case of left piping)
4
Disconnect the pipe
connection with 2 pair
of spanners.
Caution
From the point of view
of environmental
protection, be sure to
use a vacuum pump
for air purging.
203
Warning
Be sure to turn off all power supplies at least 10 minutes before
disassembling work.
Procedure
Drain hose
Points
When reassembling, make
sure the drain hose is
sloped downward.
Gas pipe
Liquid pipe
Insulation tape
(R10322)
Caution
In pump-down work, be sure
to stop the compressor
before disconnecting the
refrigerant pipe. If the
refrigerant pipe is
disconnected with the
compressor being operated
and the stop valve being
open, air may be sucked in to
(R10323)
generate an over-pressure in
refrigeration cycle, thus
resulting in pipe rupture or
accidental injury.
Place a plastic bag under
the drain pan to prevent
from wetting the floor with
remaining drain.
If the drain hose is
embedded in the wall,
disconnect the drain hose
beforehand.
(R10324)
Carry out the removal works
with 2 pair of spanners.
When the pipes are
disconnected, protect the
both openings of pipe side
and unit side from entering
of moisture.
(R10325)
Removal Procedure
SiBE12-908
Connection wire
Drain hose
Humidifying
hose
(R10879)