Removal Of The Fan-Valve-Duct Assy - Daikin CTXU25G2V1B Service Manual

Inverter multi system with humidifying
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

Outdoor Unit
2.5

Removal of the Fan-valve-duct ASSY

Procedure
Step
Remove the 7 screws
1
of the fan-valve-duct
ASSY.
225
Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Duct (adsorption side)
Fan-valve-duct ASSY
Heater
ASSY
Humidifying
rotor motor
Harness ASSY
(R10349)
(R0242)
Fan-valve-duct ASSY
SiBE12-908
Points
Preparation
Remove the heater ASSY
and the humidifying rotor.
The humidifying rotor is
located under the heater
ASSY and the duct.
Do not dismantle the
fan-valve-duct ASSY.
Replace it as a unit.
Removal Procedure