Dc Voltage / Dc Current Sensor Abnormality - Daikin CTXU25G2V1B Service Manual

Inverter multi system with humidifying
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

Troubleshooting

2.26 DC Voltage / DC Current Sensor Abnormality

H8
Remote
Controller Display
Method of
DC voltage or DC current sensor system abnormality is identified based on the compressor
operation frequency and the input current detected by the product of DC current and DC
Malfunction
voltage.
Detection
Malfunction
When the compressor operation frequency is more than 56 Hz (40 class) or 40 Hz (50 class),
and when the input current is less than 0.25 A
Decision
(Input current is below 0.5 A)
Conditions
Supposed
Causes
Troubleshooting
Replace the outdoor unit PCB.
145
The unit shuts down when the fault occurs 4 times.
Fault counter is reset to zero if the unit does not stop during accumulated compressor
operation time of 60 minutes after restored from fault conditions.
Defective outdoor unit PCB
Defective current transformer
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
SiBE12-908