SiBE12-908
1. Indoor Unit
1.1
Removal of Air filter
Procedure
Step
1. Appearance feature
2. Removing the air filter
1
Hold the right and left
projections of the front
panel, and open the
panel to the position
where it stops.
2
Slightly push up the
knob at the center of
the air filter and release
the hook.
Pull out the air filter
3
downwards and remove
it.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Signal reciever
ON / OFF switch
Room temterature and humidity sensors
Front panel
"LEFT"
mark
Dangerous: High voltage
A high voltage is applied to
all the electric circuits of this
product including
thermistors.
(R10277)
Multi-colored
indicator lamp
TIMER lamp
INTELLIGENT
EYE lamp
INTELLIGENT
EYE
(R10278)
(R10279)
Air filter
(R10280)
Indoor Unit
Points
Warning
When a signal from the
remote controller is
received, the receiving tone
sounds and the operation
lamp flickers immediately to
confirm the signal reception.
When the ON/OFF switch is
kept pressed for 5 seconds,
the forced cooling operation
is performed for about 15
minutes.
The air filter is marked for
difference between the right
and left sides.
The left filter has the "LEFT"
mark.
Insert the air filter with the
"FRONT" mark faced up.
The air filter can be set
easily by inserting it along
the guides.
Be sure to insert the hooks
(at 2 lower positions) when
mounting the air filter.
182