Thermostat Control - Daikin CTXU25G2V1B Service Manual

Inverter multi system with humidifying
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

SiBE12-908
1.2

Thermostat Control

Thermostat control is based on the difference between the room temperature and the set point.
Thermostat OFF Condition
Thermostat ON Condition
Cooling / Dry
Heating
Function and Control
The temperature difference is in the zone A.
The temperature difference is above the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
C
B
A
A
B
C
Room temperature - set point
ON
Cooling : –0.5°C
Dry : –0.5°C
Cooling : –2.0°C
Dry : –2.5~–2.0°C
OFF
Room temperature - set point
OFF
2.0°C
0.5°C
ON
Main Functions
(R4668)
(R9424)
16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ctxu35g2v1b2mxu40gv1bCtxu42g2v1b2mxu50gv1bCtxu50g2v1b

Table of Contents